Technical Data; Technical Considerations; Features And Specifications; M250 And M215 Features And Compliance - enphase M250 Installation And Operation Manual

M-series enphase microinverter
Hide thumbs Also See for M250:
Table of Contents

Advertisement

Technical Data

Technical Considerations

Be sure to verify the voltage and current specifications of your PV module match those of the
microinverter. For more information, refer to our
WARNING: Risk of equipment damage. You must match the DC operating voltage
range of the PV module with the allowable input voltage range of the Enphase
Microinverter.
WARNING: Risk of equipment damage. The maximum open circuit voltage of the PV
module must not exceed the specified maximum input voltage of the Enphase
Microinverter.
The output voltage and current of the PV module depends on the quantity, size and temperature of the
PV cells, as well as the insolation on each cell. The highest PV module output voltage occurs when the
temperature of the cells is the lowest and the PV module is at open circuit (not operating). The maximum
short circuit current rating of the PV module must be equal to or less than the maximum input DC short
circuit current rating of the microinverter.

Features and Specifications

M250 and M215 Features and Compliance

Enclosure environmental rating
Connector types
Cooling
Communication
ADD pollution rating
Grid Compliance
Other Compliance
Automatic disconnect
Integrated AC disconnect
Protective class
33
module compatibility
Features and Compliance
IP67
Order with MC-4 Type 2 locking or Amphenol H4 connectors
Convective – no fan
Power line
2
France VDE0126
Belgium C10_11
Italy CEI_0-21
Luxembourg VDE0126
Luxembourg C10_11
Netherlands EN50438
United Kingdom G83/2, G59/2
Australia AS4777
Directive 2006/95/EC,
Directive 2004/108/EC,
EN 50065-1:2001
EN 50065-2-1:2003
EN 50065-2-2:2003
EN 50065-2-3:2003
EN 61000-3-2:2006
EN 61000-3-3:1995
EN 61000-6-1:2007
EN 61000-6-2:2005
EN 61000-6-3:2007
EN 61000-6-4:2007
EN 62109-1:
EN 62109-2: 2009
VDE-0126-1-1
C10/11
With automatic disconnection device according to OVE / ÖNORM E 8001-4-712
The AC connector has been evaluated and approved for use as the required
load-break disconnect.