Application Examples
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U - I
A53
Table 6.4 Analog Speed Reference (Current)
FC
+24 V
12
+24 V
13
18
D IN
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.5 Start/Stop Command with Safe Stop
inverter.ru
(812) 702-47-50
VLT Refrigeration Drive Operating Instructions
P P arameters
Function
6-12 Terminal 53
4 mA*
Low Current
6-13 Terminal 53
20 mA*
High Current
6-14 Terminal 53
0 Hz
Low Ref./Feedb.
Value
6-15 Terminal 53
50 Hz
High Ref./Feedb.
Value
+
* = Default Value
Notes/comments:
-
4 - 20mA
P P arameters
Function
5-10 Terminal 18
[8] Start*
Digital Input
5-12 Terminal 27
[0] No
Digital Input
operation
5-19 Terminal 37
[1] Safe Stop
Safe Stop
Alarm
* = Default Value
Notes/comments:
If 5-12 Terminal 27 Digital Input
is set to [0] No operation, a
jumper wire to terminal 27 is
not needed.
MG16J102 - VLT is a registered Danfoss trademark
Speed
Setting
Start (18)
Illustration 6.1 Start/Stop Command with Safe Stop
FC
12
+24 V
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
Setting
55
A OUT
42
COM
39
Table 6.6 Pulse Start/Stop
Speed
Latched Start (18)
Stop Inverse (27)
Illustration 6.2 Latched Start/Stop Inverse
P P arameters
Function
Setting
5-10 Terminal 18
[9] Latched
Digital Input
Start
5-12 Terminal 27
[6] Stop
Digital Input
Inverse
* = Default Value
Notes/comments:
If 5-12 Terminal 27 Digital Input
is set to [0] No operation, a
jumper wire to terminal 27 is
not needed.
47
6
6