If acceleration problems were encountered
• •
If warnings or alarms occur, see 8 Warnings and
Alarms
Check that motor data is entered correctly
Increase the ramp-up time accel time in
3-41 Ramp 1 Ramp Up Time
Increase current limit in 4-18 Current Limit
Increase torque limit in 4-16 Torque Limit Motor
Mode
If deceleration problems were encountered
If warnings or alarms occur, see 8 Warnings and
Alarms.
Check that motor data is entered correctly.
Increase the ramp-down time decel time in
3-42 Ramp 1 Ramp Down Time.
Enable overvoltage control in 2-17 Over-voltage
Control.
See 4.1.1 Local Control Panel for resetting the frequency
converter after a trip.
NOTE
3.2 Applying Power to 3.3 Basic Operational Programming
conclude the procedures for applying power to the
frequency converter, basic programming, set-up and
functional testing.

3.7 System Start Up

The procedure in this section requires user-wiring and
application programming to be completed. 6 Application
Examples is intended to help with this task. Other aids to
application set-up are listed in 1.3 Additional Resources. The
following procedure is recommended after application set-
up by the user is completed.
CAUTION
MOTOR START!
Ensure that the motor, system and any attached
equipment is ready for start. It is the responsibility of the
user to ensure safe operation under any condition. Failure
to do so could result in personal injury or equipment
damage.
1.
Press [Auto On].
2.
Ensure that external control functions are
properly wired to the frequency converter and all
programming is completed.
3.
Apply an external run command.
inverter.ru
(812) 702-47-50
VLT Refrigeration Drive Operating Instructions
If warnings or alarms occur, see 8 Warnings and Alarms.
MG16J102 - VLT is a registered Danfoss trademark
4.
Adjust the speed reference> throughout the
speed range.
5.
Remove the external run command.
6.
Note any problems.