Danfoss VLT FC 103 Operating Instructions Manual page 77

Refrigeration drive
Hide thumbs Also See for VLT FC 103:
Table of Contents

Advertisement

Specifications
Protection and Features
• •
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the frequency converter trips if the temperature reaches 95
C 5 C. An overload temperature cannot be reset until the temperature of the heatsink is below 70 C 5 C
(Guideline - these temperatures may vary for different power sizes, enclosures etc.). The frequency converter has
an auto derating function to avoid its heatsink reaching 95 C.
The frequency converter is protected against short-circuits on motor terminals U, V, W.
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit
voltage is too low or too high.
The frequency converter is protected against earth (ground) faults on motor terminals U, V, W.
inverter.ru
(812) 702-47-50
VLT Refrigeration Drive Operating Instructions
MG16J102 - VLT is a registered Danfoss trademark
10
10
73