Basic Concepts for Programming an S7-200 CPU
4.11
Background Time
You can configure the percentage of the scan cycle that will be dedicated to
processing communications requests that are associated with a RUN mode edit
compilation or STL status gathering. As you increase the percentage of time that is
dedicated to processing communication requests, you increase scan time, which
makes your control process run more slowly.
Select the Background Time tab to set the scan cycle time-slice that is allowed for
background communications (Figure 4-24). Edit the properties for the
communications background time and then download the modifications to the
CPU.
The default percentage of the scan dedicated to processing communications
requests is set to 10%. This setting was chosen to provide a reasonable
compromise for processing compilation/status operations while minimizing the
impact to your control process. You can adjust this value by 5% increments up to a
maximum of 50%.
System Block
Port(s)
Analog Input Filters
Select Communication Background Time (5 - 50%)
10
Default = 10%
Configuration parameters must be downloaded before they take effect.
Not all PLC types support every System Block option. Press F1 to see
which options are supported by each PLC.
Figure 4-24
4-42
Retentive Ranges
Password
Pulse Catch Bits

Background Time Configuration Screen

Output Table
Input Filters
Background Time
OK
S7-200 Programmable Controller System Manual
Cancel
A5E00066097-02