And Double Word, Or Double Word, Exclusive Or Double Word - Siemens SIMATIC S7-200 System Manual

Hide thumbs Also See for SIMATIC S7-200:
Table of Contents

Advertisement

SIMATIC Instructions

And Double Word, Or Double Word, Exclusive Or Double Word

L
WAND_DW
A
EN
D
F
IN1
B
D
IN2
WOR_DW
EN
IN1
IN2
WXOR_DW
EN
IN1
IN2
S
ANDD
T
L
ORD
XORD
221
222 224
Inputs/Outputs
IN1, IN2
VD, ID, QD, MD, SD, SMD, AC, LD, HC, Constant, *VD, *AC, SD,
*LD
OUT
VD, ID, QD, MD, SMD, LD, AC, *VD, *AC, SD, *LD
9-116
The And Double Word instruction ANDs the
corresponding bits of two double word inputs and loads
ENO
the result (OUT) in a double word.
The Or Double Word instruction ORs the corresponding
OUT
bits of two double word inputs and loads the result (OUT)
in a double word.
The Exclusive Or Double Word instruction XORs the
ENO
corresponding bits of two double word inputs and loads
the result (OUT) in a double word.
OUT
Error conditions that set ENO = 0: SM4.3 (run-time),
0006 (indirect address)
These instructions affect the following Special Memory
ENO
bits: SM1.0 (zero)
OUT
IN1, OUT
IN1, OUT
IN1, OUT
226
Operands
S7-200 Programmable Controller System Manual
Data Types
DWORD
DWORD
A5E00066097-02