Setting Up Communications Hardware and Network Communications
This configuration allows only one master device and supports only the PPI
protocol. In order to communicate through the PPI interface, the S7-200 PLC
requires that the modem use an 11-bit data string. In this mode, the S7-200
controller requires one start bit, eight data bits, one parity bit (even parity), one
stop bit, asynchronous communication, and a transmission speed of 9600/19,200
baud. Many modems are not capable of supporting this data format. The modem
requires the settings listed in Table 7-4.
Figure 7-20 shows the pin assignments for a null modem adapter and a 25-pin to
9-pin Adapter.
Table 7-4

Modem Settings Required for an 11-Bit Modem

Modem
8 data
1 start
11 Bit
11-Bit
1 stop
1 parity (even)
Null Modem Adapter
Modem
25-pin
Figure 7-20
7-26
Transmission
Data Format
Speed between
in Bits
Modem and PC
9600 baud
19 200 baud
19,200 baud
25-pin
2
2
3
3
4
4
5
5
6
6
7
7
8
8
20
20

Pin Assignments for a Null Modem Adapter and a 25-Pin to 9-Pin Adapter

Transmission
Other Features
Speed on
the Line
Ignore DTR signal
No hardware flow
9600 baud
control
19 200 baud
19,200 baud
No software flow
control
25-Pin to 9-Pin Adapter
PC/PPI cable
25-pin
9-pin
2
2
3
3
4
7
7
5
S7-200 Programmable Controller System Manual