Emerson RTS FQ Operating Manual page 78

Fail-safe quarter-turn actuator
Table of Contents

Advertisement

User Instructions
Part Number IOM – 87376-7
RTS FQ
TYPE
Max Electric Torque
Max Fail-safe Torque
Modulating Torque
Fail-safe Function
Fail-safe Trigger
Positioning Speed - Electric
Positioning Speed - Fail-safe
Available Travel
Mode of Operation
Manual Override
VALVE-MOUNTING
Flange
Max Stem Diameter
Max Square (Flats)
ENVIRONMENTAL CONDITIONS
Weather Protection
Ambient Temperature
Corrosion Protection
Painting/Color
Weight approx.
MOTOR - BRUSHLESS TECHNOLOGY
Isolation Class
Power Supply
Power Comsumption Idle with
Fail-safe Brake
ACTUATOR CONTROL
Technology Integrated processor control unit with frequency technology for variable speed control
Control Elements
Local Display Backlit LCD display, can be rotated in 90 degree steps
LEDs 4 programmable red, green, blue LEDs for operation - readiness - warning - and error messages
Communication Infrared communication interface and bluetooth technology including ANDROID App for simple configuration
Inputs
Outputs
FUNCTIONS
Standard
ELECTRICAL CONNECTION
Cable Entry
FQ-03
max. lbs. ft (Nm)
220 (300)
max. lbs. ft (Nm)
110 (150)
max. lbs. ft (Nm)
110 (150)
sec
15 to 400
sec
°
On/off Duty
Modulating Duty
ISO 5210
F07/F10
in (mm)
in (mm)
0.86 (22)
lb. (kg)
94 (43)
V
24 VDC or 115-230 VDC or 1x 115-230 VAC, 50-60Hz or 3x 380-480 VAc, 50-60 Hz
Nominal Current
With additional language independent symbols
·
Selector switch LOCAL - OFF - REMOTE (lockable)
·
Control switch OPEN - STOP - CLOSE contact less sensor technology
·
5 configurable binary (discrete inputs) control inputs:
·
OPEN - STOP - CLOSE - EMERGENCY OPEN - EMERGENCY CLOSE
Nominal voltage 24VDC
·
· 8 configurable binary (relay) outputs:
READY - OPEN - CLOSE - RUNNING OPEN - RUNNING CLOSE - TORQUE - LOCAL - REMOTE
Power supply 24 VDC +/– 6V (selectable internal or external)
·
· Switch-off mode adjustable, travel or torque dependent
· Torque adjustable: 25-100% of max. torque
· Adjustable speed for process optimization and emergency speeds
· Password protection (reading and/or writing)
· Multi-language display
· Status indication for binary inputs/outputs and analog signals on LCD Display
· Data logging for analysis and service
· Motor protection by Positive Temperature Coefficient sensors
3 metric threaded boreholes for cable grands: M40x1.5 / M32x1.5 / M25x1.5
(Optional: 2x NPT1/2" + 1xNPT1")
FQ-06
440 (600)
220 (300)
220 (300)
Selectable opening and closing (CW/CCW)
Loss of 24 V DC Fail-safe signal or main power supply (selectable)
15 to 400
1 - 5
1 - 5
90 +/– 5° with mechanical end-stop
S2–15 min
S4 – 1200 starts/hour – 40% duty cycle
Optional
F10/F12
1 (25)
1.58 (40)
1.25 (32)
IP 67 /NEMA 4 (Optional IP 68/NEMA 6)
- 40° C (-40°F) to +60°C (140°F)
K2 for aggressive atmospheres
Two component painting / RAL 7024
116 (53)
Insulation class F, max. 155° C (311°F) permanent temperature
2.5 A
40 W
July 2016, Rev 1.
FQ-20
1,475 (2,000)
730 (1,000)
730 (1,000)
25 to 650
4 - 15
F14/F16
2.36 (60)
1.87 (46)
440 (200)
71