Fail-safe quarter-turn actuator
Table of Contents

Advertisement

User Instructions
Part Number IOM – 87376-7
Table 14.
P9.1
Binary Inputs Table
Menu
Sub Menu
Item
Item
Binary
Input 1
Input
Poss. Setting
0: No
This input has no function
Function
OPEN command in REMOTE mode (selector
1: Open
switch in position REMOTE).
CLOSED command in REMOTE mode (selector
2: Closed
switch in position REMOTE).
STOP command in REMOTE mode (selector
3: Stop
switch in position REMOTE).
Self-hold for OPEN, i.e., a short pulse is sufficient
4: Open
and the actuator moves then into the end
Self-hold
position. Use the STOP command to stop the
actuator.
5: Closed
Self-hold for CLOSED, see OPEN SELF-HOLD
Self-hold
Superimposed run command; run the actuator in
6: Emergency
direction OPEN regardless of whether the
Open
selection switch is set to REMOTE or LOCAL
operation.
Superimposed run command; run the actuator in
7: Emergency
direction CLOSED regardless of whether the
Closed
selection switch is set to REMOTE or LOCAL
operation.
The actuator may be operated only with a
8: Release
switched.
9: Open/
The actuator moves towards OPEN if input is
Closed
active and towards CLOSED otherwise.
10: Close
The actuator moves towards CLOSED if input is
Open
active and towards OPEN otherwise.
11: Postioner Release of the postioner
12: Open
As OPEN but active low
inverted
13: Zu inv.
As CLOSED but active low
14: Stop inv.
As STOP but active low
15: Open
As OPEN Self-Hold but active low
Self- Hold inv.
16: Closed
As CLOSED Self-Hold but active low
Self-Hold inv.
17:
Emergency-
As EMERGENCY OPEN but active low
Open inv.
18:
Emergency-
As EMERGENCY CLOSED but active low
Closed inv.
July 2016, Rev 1.
Notes/Comments
47