User Instructions
Part Number IOM – 87376-7
CAUTION: OBSERVE PROPER POSITIONING
Generally, 100% stands for fully open and 0% for fully closed. Please note that these values
cannot be changed.
Table 7.
P1.1
P1.2
P1.3
P1.4
P1.5
P1.6
P1.7
P1.8
CAUTION: OBSERVE LIMITS AND FACTORS OF GEAR
When installing the actuator on an gear or a thrust unit, please take into account the limits and
factors of the gear/thrust unit at parameterization.
When using end limit switch off by torque, the end position limit must be set before reaching
the torque limit. Accordingly, the actuator will only signal the final end position if the
configured torque and the associated end position are reached. If the end position is not
reached, a torque error is reported (see
42
End Limit Table
Sub Menu
Menu Item
Item
End limit
Open
End limit
Close
Switch off
End limit
Open
Switch off
End limit
Close
Closing
End limit
directing
Rotate sense
End limit
position
End limit
LED function
End limit
End limit
hysteresis
Poss. Setting
The parameter value can be set using TEACHIN.
TEACHIN;
With a known travel, the second end position can be
0-100U1)
entered after setting the first end position.
The parameter value can be set using TEACHIN.
TEACHIN;
With a known travel, the second end position can be
0-100U1)
entered after setting the first end position.
The actuator uses end position signals to switch off and
by travel (0)
report the end position.
The actuator signals the end position or stops the motor
only after reaching the specified torque with the proviso
by torque (1)
that it has reached the end position. If the end position
signal is not reached, the actuator reports an error.
The actuator uses end position signals to switch off and
by travel (0)
report the end position.
The actuator signals the end position or stops the motor
only after reaching the specified torque with the proviso
by torque (1)
that it has reached the end position. If the end position
signal is not reached, the actuator reports an error.
right (0)
Actuator is designed for clockwise = closing
Reverse direction of rotation. Counterclockwise = closing.
left (1)
The crossing of all signals and commands is performed by
the controller.
0
No function at RTS FQ Fail-Safe Quarter-Turn Series.
1
Close = green (0) Definition of the LED colour of the CLOSED or OPEN end
position signalization.
Close = red (1)
Hysteresis range for end position signals, Example:
End position hysteresis 1% means, that the end position
0,1 - 10,0%
OFF is reached when closing 0%, and will leave it when
opening only at 1%, i.e., a reclosing can only take place
after leaving this hysteresis.
Section
17.2.2).
July 2016, Rev 1.0
Notes /Comments