1.
Because of small leakage currents generated by the EMI filter in the UPS it is necessary to double check that the ground wire of the
UPS is properly grounded before connecting the UPS to the AC mains.
2.
To ensure safety in all applications where a UPS is hard wired to the electrical supply, ensure that the system is installed by a
qualified electrical contractor.
3.
The UPS has its own internal energy source (battery). Should the battery be switched on when no AC power is available there could
be voltage at the output terminals.
4.
Make sure that the AC utility outlet is correctly grounded.
5.
Do not open the case as there are no serviceable parts inside. Opening the case voids the warranty.
6.
Do not try to repair the unit yourself; contact your local supplier. Repairing the unit yourself voids the warranty.
7.
Please make sure that the input voltage of the UPS matches the supply voltage.
8.
Use a certified input power cable with the correct plugs and sockets for the appropriate system voltage.
9.
To prevent any overheating of the UPS keep all ventilation openings free from obstruction, and do not store things on top of the UPS.
Keep the UPS 30 cm away from the wall.
10. Ensure that the UPS is installed within the proper environmental range. (0-40 ° C and 0-90% non-condensing humidity)
11. Do not install the UPS in direct sunlight. Your warranty may be void if the batteries fail.
12. Install the UPS indoors as it is not designed for installation outdoors.
13. Dusty, corrosive and salty environments can damage any UPS.
14. Install the UPS away from objects that give off excessive heat and areas that are excessively wet.
15. If liquids are spilt onto the UPS or foreign objects dropped into the unit the warranty will be null and void.
16. The battery will discharge naturally if the system is unused for a long time.
17. The UPS should be recharged every 2-3 months if unused. If this is not done then the warranty will be null and void. When installed
and being used the batteries will be automatically recharged and kept in top condition.
18. This UPS supports electronic equipment in office, telecommunication, process-control, medical, and security applications.
Non-authorized technicians are not allowed to install the UPS in the following areas.
a. Medical equipment directly related to human life.
b. Elevators, subway systems, or any other equipment related to human safety.
c. Public systems or critical computer systems.
19. Do not install the UPS in an environment with sparks, smoke or hazardous gas.
20. Make sure the UPS is completely turned off when transporting it. It might cause electrical shock if the output is not cut completely.
21. The UPS includes a Maintenance Bypass Switch. Please follow the procedures strictly when switching on or off the Maintenance
Bypass Switch.
22. The UPS offers a CVCF (Constant Voltage Constant Frequency) setting function.
a. For correct setting and wiring please contact with your local utility agent.
b. Do not set it yourself or your warranty will be void.
23. This UPS has been designed and constructed to protect your assets from the wide range of power aberrations experienced on utility
power lines today. It is your insurance for a reliable, clean and stable voltage supply. It is worth taking care to install the system
correctly and to have it maintained correctly by your local dealer.
24. SAVE THESE INSTRUCTIONS. This manual contains important instructions that should be followed during installation and
maintenance of the UPS and batteries.
25. The UPS is intended for installation in a controlled environment.
26. Install the UPS so that it is not likely to be contacted by people.
27. The maximum ambient operating temperature is 40 ° C or equivalent.
28. Units are considered acceptable for use in a maximum ambient 40°C
29. CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES
ACCORDING TO THE INSTRUCTIONS.
30. CAUTION - Do not dispose of batteries in a fire. The batteries may explode.
31. CAUTION – Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
32. CAUTION– A battery can present a risk of electrical shock and high short circuit current. The following precautions should be
observed when working on batteries:
1) Remove watches, rings, or other metal objects.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or disconnecting battery terminals.