Environmental specifications

Table 2: Standard specifications
Specification
Temperature range
Operating
Nonoperating
Relative humidity (noncondensing)
Operating
Non-Operating
1
All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 304.8 m (1.8°F per
1,000 ft) to 3,048 m (10,000 ft) is applicable. No direct sunlight allowed. Maximum rate of change is
20°C per hour (36°F per hour).
Table 3: ASHRAE Class A3 specifications
Specification
Temperature range
Operating
Nonoperating
Relative humidity (noncondensing)
Operating
Non-Operating
1
All temperature ratings shown are for sea level. Good for 40°C operation up to 1,828 m (6,000 ft) with
no altitude de-rating. No restriction on product configurations. Abnormal configurations, allowed for up
to 96 hours at one time, no more than 15 days maximum per year. Operation above 40°C (104°F) up to
55°C (131°F), no altitude de-rating, 1,828 m (6,000 ft) limit. Some components could be outside the
thermal maximum limits. System must be kept running, processor throttling is allowed. Abnormal
conditions allow for operation down to -5°C (23°F).
1
1
Value
10°C to 35°C (50°F to 95°F)
-30°C to 60°C (-22°F to 140°F)
8% to 90% at 28°C (82.4°F) maximum wet bulb
temperature
5% to 95% at 38.7°C (101.7°F) maximum wet bulb
temperature
Value
5°C to 40°C (41°F to 104°F)
-30°C to 60°C (-22°F to 140°F)
8% to 90% at 28°C (82.4°F) maximum wet bulb
temperature
5% to 95% at 38.7°C (101.7°F) maximum wet bulb
temperature