Levelflex M FMP41C, FMP45

Output signal

Signal on alarm

Linearization

Endress+Hauser

Output

• 4 to 20 mA with HART protocol
• Profibus-PA
• FOUNDATION Fieldbus (FF)
Error information can be accessed via the following interfaces:
• Local display:
– Error symbol
– Plain text display
• Current output, signal on error can be selected (e.g. according to NAMUR recommendation NE 43).
• Digital interface
The Levelflex M linearization function enables conversion of the measured value into any desired length or
volume unit, mass or %. Linearization tables for volume calculation in cylindrical tanks are pre-programmed.
Any other table from up to 32 value pairs can be input manually or semi-automatically. The creation of a
linearization table with the ToF Tool or FieldCare is particularly convenient.