10 Supplement
Long-term drift of the zero signal
Ambient conditions
Ambient, storage and transport temperature
Process conditions
The specifications to the pressure stage and the product temperature are used as an overview.
The specifications of the type label are applicable.
Process pressure, transmitter
with measuring ranges 0.1 bar (1.45 psig)
-
or 0.2 bar (2.9 psig)
with meas. ranges from 0.4 bar (5.8 psig)
-
Pressure stage, process fitting
Screw connection
-
Thread
-
Lock fitting
-
Flange 316L
-
Flange GFK
-
Product temperature, suspension cable/measuring cell seal
PE/FKM
-
PE/EPDM
-
PUR/FKM
-
PUR/EPDM
-
FEP/FKM
-
FEP/FFKM
-
FEP/EPDM
-
Product temperature, connection tube/seal meas. cell
FKM
-
FFKM
-
EPDM
-
Product temperature, transmitter protection/seal meas. cell
PVDF/FKM or EPDM
-
PVDF/FFKM
-
PE/FKM or EPDM
-
Calibration position
Influence of the installation position
64
< (0.1 % x TD)/year
-40 ... +80 °C (-40 ... +176 °F)
max. 15 bar (217.6 psig) or max. 20 bar (290 psig)
max. 25 bar (363 psig)
316L PN 3, PVDF PN 5
316L PN 25, PVDF unpressurized
unpressurized
PN 16 or PN 40
10 bar
-20 ... +60 °C (-4 ... +140 °F)
-20 ... +60 °C (-4 ... +140 °F)
-20 ... +80 °C (-4 ... +176 °F)
-20 ... +80 °C (-4 ... +176 °F)
-20 ... +100 °C (-4 ... +212 °F)
-10 ... +100 °C (+14 ... +212 °F)
-40 ... +100 °C (-40 ... +212 °F)
-20 ... +100 °C (-4 ... +212 °F)
-10 ... +100 °C (+14 ... +212 °F)
-20 ... +100 °C (-4 ... +212 °F)
-20 ... +60 °C (-4 ... +140 °F)
-10 ... +60 °C (+14 ... +140 °F)
-20 ... +60 °C (-4 ... +140 °F)
upright, diaphragm points downward
< 0.2 mbar/20 Pa (0.003 psig)
Limited by the overpressure resistance of the measuring cell.
11)
Limitation by the pressure-tightness of the cable connection.
12)
Limited by the overpressure resistance of the measuring cell.
13)
12)
13)
VEGABAR 66 • 4 ... 20 mA/HART