Motor Temperature Control Menu - Curtis 1232E Manual

Enhanced ac controllers for induction motors and surface permanent magnet motors
Hide thumbs Also See for 1232E:
Table of Contents

Advertisement

PARAMETER
Sensor Enable
MotorTemp_Sensor_Enable
OptionBits3 [Bit 1]
0x306C 0x00
Sensor Type
MotorTemp_Sensor_Type
0x307B 0x00
Sensor Temp Offset
MotorTemp_Sensor_Offset
0x304A 0x00
Braking Thermal Cutback Enable
BrakingThermalCutback_Enable
BrakingThermalCutback_Enable_
Bit0 [Bit0]
0x386C 0x00
Temperature Hot
MotorTemp_Hot
0x304E 0x00
Temperature Max
MotorTemp_Max
0x304F 0x00
MotorTemp LOS Max Speed 100–3000 rpm
MotorTemp_LOS_Max_Speed
0x308A 0x00
Curtis 1232E/34E/36E/38E & 1232SE/34SE/36SE Manual,
2 4 N O V E M B E R 2 0 1 5
3 — PROGRAMMABLE PARAMETERS:

MOTOR TEMPERATURE CONTROL MENU

ALLOWABLE
RANGE
On/Off
When programmed On, the motor temperature cutback and the motor
temperature compensation features are enabled. This parameter can be
On/Off
used only if a temperature sensor has been properly configured.
The motor temperature cutback feature will linearly cut back the
current from 100% to 0% between the Temperature Hot and Temperature
Max temperatures. The motor temperature compensation feature will adapt
the motor control algorithms to varying motor temperatures, for improved
efficiency and more consistant performance.
1–5
Five sensor types are predefined in the software:.
Type 1 KTY83–122
1–5
Type 2 2× Type 1, in series
Type 3 KTY84–130 or KTY84–150
Type 4 2× Type 3, in series
Type 5 PT1000.
Custom sensor types can be set up easily, if none of the five predefined
types is appropriate for your application. Please contact your Curtis
distributor or support engineer.
Note: The industry standard KTY temperature sensors are silicon
+
temperature sensors with a polarity band; the polarity band of a KTY
sensor must be the end connected to I/O Ground (pin 7).
-20 – 20 °C
Often the sensor is placed in the motor at a location with a known offset
to the critical temperature; the offset can be corrected with this parameter.
-200–200
The parameter can also be used to correct a known offset in the sensor itself.
On/Off
When programmed On, drive current and all forms of regen braking current
will be cut back based on motor temperature. All forms of regen braking
On/Off
current (Regen_Current_Limit, Brake_Current_Limit, EMR_Current_Limit,
Interlock_Brake_Current_Limit) includes emergency reverse braking,
interlock braking, brake input braking, direction reversal braking, neutral
braking, and speed limit braking.
When programmed Off, only drive current (and not the regen braking
currents) will be cut back based on motor temperature.
If the vehicle has mechanical brakes, setting this parameter to On may
help reduce motor heating.
0–250 °C
Defines the temperature at which current cutback begins.
0–2500
0–250 °C
Defines the temperature at which current is cut back to zero.
0–2500
When a Motor Temp Sensor Fault (fault code 29) is set, a LOS (Limited
100–3000
Operating Strategy) mode is engaged. The maximum speed is reduced to
the programmed Max Speed in the operating mode (Max_Speed_SpdMx,
Max_Speed_SpdM, Max_Speed_TrqM) or to the MotorTemp_LOS_Max_
Speed, whichever is lower.
DESCRIPTION
30
os
Motor Temperature Parameters
63