Optimum Start / Stop Control; Increase Of Reduced Setpoint - Siemens Albatros2 RVS46 User Manual

Zone controler
Hide thumbs Also See for Albatros2 RVS46:
Table of Contents

Advertisement

Optimum start / stop control

Optimum start control max
Optimum stop control max

Increase of Reduced setpoint

62/100
Siemens Schweiz AG
HVAC Products
Line no.
HC1
HC2
HCP
790
1090
1390
791
1091
1391
The change from one temperature level to the other is optimized in a way that the
Comfort setpoint will be reached at the relevant switching time.
The change from one temperature level to the other is optimized in a way that the
Comfort setpoint minus 1/4 °C will be reached at the relevant switching time.
Optimum start / stop control is possible with or without room sensor
0
Xein
TRx
TRw
Xein
Switch-on time shifted forward
Xaus
Switch-off time shifted forward
ZSP
Time program
TRx
Actual value room temperature
TRw
Room temperature setpoint
Line no.
HC1
HC2
HCP
800
1100
1400
801
1101
1401
The function is used primarily in connection with heating systems having little spare
capacity (e.g. low-energy houses). In that case, the heating up time would be too long if
outside temperatures are low. When the Reduced setpoint is raised, the rooms are
prevented from cooling down to too low levels, thus shortening the heating up time
when changing to the Comfort setpoint.
User Manual
The settings in detail
Operating line
Optimum start control max
Optimum stop control max
ZSP
Operating line
Red setpoint increase start
Red setpoint increase end
Xaus
1/4 °C
22. November 2006
24
CE1U2353en