ECO functions

Summer/winter heating
limit
24-hour heating limit
58/100
Siemens Schweiz AG
HVAC Products
Line no.
HC1
HC2
HCP
730
1030
1330
732
1032
1332
The summer / winter heating limit is used to switch the heating on and off in the course
of the year, depending on the temperature conditions. In "Automatic" mode, switching
on / off takes place automatically, so there is no need for the user to do this manually.
By changing the setting, the respective periods of time will be shortened or extended.
Increase:
Winter operation will start earlier
Summer operation will start later
Decrease:
Winter operation will start later
Summer operation will start earlier
• The function is not active in operating mode "Continuously Comfort temperature"
• The display will show ECO
• To give consideration to the building's thermal dynamics, the outside temperature will
be attenuated
Example:
T
°C
20
19
18
17
16
ON
OFF
0
5
SWHG Summer/winter heating limit
TAged Attenuated outside temperature
t
Temperature
t
Days
The 24-hour heating limit is used to switch the heating on and off in the course of the
day, depending on the outside temperature. This function is used primarily during
intermediate seasons (spring and autumn), enabling the system to respond to short-
time temperature variations.
Example:
Setting line
Comfort setpoint (TRw)
24-hour heating limit (THG)
Changeover temperature (TRw-THG) heating off
Switching differential (fixed)
Changeover temperature
User Manual
The settings in detail
Operating line
Summer/winter heating limit
24-hour heating limit
TAged
SWHG +1 °C
SWHG
SWHG -1 °C
t
10
15
heating on
e.g.
22°C
-3°C
= 19°C
-1°C
= 18°C
CE1U2353en
22. November 2006