Operating mode

Setpoints

Room temperature
Frost protection
56/100
Siemens Schweiz AG
HVAC Products

6.6 Heating circuits

For the heating circuits, there are various functions available which can be individually
set for each heating circuit.
Line no.
1300
The operating mode of heating circuits 1 and 2 is selected directly with the operating
mode button while the operating mode of heating circuit P is to be selected in
programming mode (operating line 1300).
This setting is used to switch between the different operating modes. The functionality
corresponds to operating mode selection with the operating mode button. For details,
refer to section "Operation".
Line no.
HC1
HC2
HCP
710
1010
1310
712
1012
1312
714
1014
1314
716
1016
1316
The room temperature can be shifted according to different setpoints. These setpoints
become active depending on the selected operating mode, thus producing different
temperature levels in the rooms.
The ranges of the adjustable setpoints are obtained as a result of their
interdependency. The following graph illustrates this.
0
2
4
6
TRKmax Comfort setpoint max
TRK
Comfort cooling setpoint
TRR
Reduced setpoint
TRF
Frost protection setpoint
In Protection mode, the room temperature is prevented from falling below a certain
level. This means that the frost protection setpoint of the room temperature will be
maintained.
@
User Manual
The settings in detail
Operating line
Operating mode
Protection
Automatic
Reduced
Comfort
Operating line
Comfort setpoint
Reduced setpoint
Frost protection setpoint
Comfort setpoint max
TRR
TRF
8
10
12
14
16
TRKmax
TRK
18
20
22
24
26
2358Z01
22. November 2006
°C
CE1U2353en