2 Functions
Intertrip/Remote
If the intertrip function is activated, it will automatically start when the differential
tripping
protection trips.
If the relevant binary inputs are allocated and activated by an external source, the in-
tertrip signal is transmitted as well. In this case, the signal to be transmitted can be
delayed with address 1303 T-ITRIP BI. This delay stabilizes the originating signal
against dynamic interferences which may possibly occur on the control cabling.
Address 1304 T-ITRIP PROL BI is used to extend a signal after it has been effec-
tively injected from an external source.
The reaction of a device when receiving an intertrip/remote tripping signal is set at
address 1302 I-TRIP RECEIVE. If it is supposed to cause tripping, set the value
Trip. If the received signal, however, is supposed to cause an alarm only, Alarm
only must be set if this indication is to be further processed externally.
The setting times depend on the individual case of application. A delay is necessary if
the external control signal originates from a disturbed source and a restraint seems
appropriate. Of course, the control signal has to be longer than the delay for the signal
to be effective. If the signal is processed externally at the receiving end, a prolongation
time might become necessary for the transmitting end so that the reaction desired at
the receiving end can be executed reliably.
2.4.3

Settings

Addr.
Parameter
1301
I-TRIP SEND
1302
I-TRIP RECEIVE
1303
T-ITRIP BI
1304
T-ITRIP PROL BI
2.4.4

Information List

No.
Information
3501
>Intertrip L1
3502
>Intertrip L2
3503
>Intertrip L3
3504
>Intertrip 3pol
3505
ITrp.rec.PI1.L1
3506
ITrp.rec.PI1.L2
3507
ITrp.rec.PI1.L3
3511
ITrp.sen.PI1.L1
3512
ITrp.sen.PI1.L2
3513
ITrp.sen.PI1.L3
3517
ITrp. Gen. TRIP
3518
ITrp.TRIP 1p L1
78
Setting Options
YES
NO
Alarm only
Trip
0.00 .. 30.00 sec
0.00 .. 30.00 sec
Type of In-
formation
SP
I.Trip: >Intertrip L1 signal input
SP
I.Trip: >Intertrip L2 signal input
SP
I.Trip: >Intertrip L3 signal input
SP
I.Trip: >Intertrip 3 pole signal input
OUT
I.Trip: Received at Prot.Interface 1 L1
OUT
I.Trip: Received at Prot.Interface 1 L2
OUT
I.Trip: Received at Prot.Interface 1 L3
OUT
I.Trip: Sending at Prot.Interface 1 L1
OUT
I.Trip: Sending at Prot.Interface 1 L2
OUT
I.Trip: Sending at Prot.Interface 1 L3
OUT
I.Trip: General TRIP
OUT
I.Trip: TRIP - Only L1
Default Setting
NO
State of transmit. the intertrip
command
Trip
Reaction if intertrip command is
receiv.
0.02 sec
Delay for intertrip via binary input
0.00 sec
Prolongation for intertrip via
bin.input
Comments