Siemens siprotec 7SD610 User Manual page 385

Differential protection
Hide thumbs Also See for siprotec 7SD610:
Table of Contents

Advertisement

Addr.
Parameter
2624
I> Telep/BI
2625
I> SOTF
2630
Iph> STUB
2631
T Iph STUB
2632
3I0> STUB
2633
T 3I0 STUB
2634
I-STUB Telep/BI
2635
I-STUB SOTF
2640
Ip>
2642
T Ip Time Dial
2643
Time Dial TD Ip
2646
T Ip Add
2650
3I0p PICKUP
2652
T 3I0p TimeDial
2653
TimeDial TD3I0p
2656
T 3I0p Add
2660
IEC Curve
2661
ANSI Curve
2670
I(3I0)p Tele/BI
2671
I(3I0)p SOTF
2680
Direction Iph>
2681
Iph> Dir.
2682
T Iph> Dir.
2683
Direction 3I0>
2684
3I0> Dir.
2685
T 3I0> Dir.
2686
I>Dir.Telep/BI
2687
I> Dir. SOTF
2688
Direction IP
2689
Ip> Dir.
2690
T Ip Dir.
7SD610 Manual
C53000-G1176-C145-4
Function
C
Setting Options
Back-Up O/C
NO
YES
Back-Up O/C
NO
YES
0.10 .. 25.00 A; ∞
Back-Up O/C
1A
0.50 .. 125.00 A; ∞
5A
0.00 .. 30.00 sec; ∞
Back-Up O/C
0.05 .. 25.00 A; ∞
Back-Up O/C
1A
0.25 .. 125.00 A; ∞
5A
0.00 .. 30.00 sec; ∞
Back-Up O/C
Back-Up O/C
NO
YES
Back-Up O/C
NO
YES
0.10 .. 4.00 A; ∞
Back-Up O/C
1A
0.50 .. 20.00 A; ∞
5A
0.05 .. 3.00 sec; ∞
Back-Up O/C
0.50 .. 15.00 ; ∞
Back-Up O/C
Back-Up O/C
0.00 .. 30.00 sec
0.05 .. 4.00 A; ∞
Back-Up O/C
1A
0.25 .. 20.00 A; ∞
5A
0.05 .. 3.00 sec; ∞
Back-Up O/C
0.50 .. 15.00 ; ∞
Back-Up O/C
Back-Up O/C
0.00 .. 30.00 sec
Back-Up O/C
Normal Inverse
Back-Up O/C
Very Inverse
Extremely Inv.
LongTimeInverse
Back-Up O/C
Inverse
Back-Up O/C
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Back-Up O/C
NO
YES
Back-Up O/C
NO
YES
Back-Up O/C
Non-Directional
Forward
Reverse
0.10 .. 25.00 A; ∞
Back-Up O/C
1A
0.50 .. 125.00 A; ∞
5A
0.00 .. 30.00 sec; ∞
Back-Up O/C
Back-Up O/C
Non-Directional
Forward
Reverse
0.05 .. 25.00 A; ∞
Back-Up O/C
1A
0.25 .. 125.00 A; ∞
5A
0.00 .. 30.00 sec; ∞
Back-Up O/C
Back-Up O/C
NO
YES
Back-Up O/C
NO
YES
Back-Up O/C
Forward
Reverse
0.10 .. 4.00 A; ∞
Back-Up O/C
1A
0.50 .. 20.00 A; ∞
5A
0.05 .. 3.00 sec; ∞
Back-Up O/C
Default Setting
NO
Instantaneous trip via Tele-
prot./BI
NO
Instantaneous trip after Switch-
OnToFault
1.50 A
Iph> STUB Pickup
7.50 A
0.30 sec
T Iph STUB Time delay
0.20 A
3I0> STUB Pickup
1.00 A
2.00 sec
T 3I0 STUB Time delay
NO
Instantaneous trip via Tele-
prot./BI
NO
Instantaneous trip after Switch-
OnToFault
∞ A
Ip> Pickup
∞ A
0.50 sec
T Ip Time Dial
5.00
Time Dial TD Ip
0.00 sec
T Ip Additional Time Delay
∞ A
3I0p Pickup
∞ A
0.50 sec
T 3I0p Time Dial
5.00
Time Dial TD 3I0p
0.00 sec
T 3I0p Additional Time Delay
Normal Inverse
IEC Curve
Inverse
ANSI Curve
NO
Instantaneous trip via Tele-
prot./BI
NO
Instantaneous trip after Switch-
OnToFault
Non-Directional
Direction of stage Iph> Dir.
1.50 A
Iph> directional Pickup
7.50 A
0.50 sec
T Iph> Dir. Time delay
Non-Directional
Direction of stage 3I0> Dir.
0.20 A
3I0> directional Pickup
1.00 A
2.00 sec
T 3I0> Dir. Time delay
NO
Instantaneous trip via Tele-
prot./BI
NO
Instantaneous trip after Switch-
OnToFault
Forward
Direction of stage Ip> Dir.
∞ A
Ip> directional Pickup
∞ A
0.50 sec
T Ip Dir.: Inv.-Time delay for IEC-
Char.
A.7 Settings
Comments
385