4 Technical Data
4.11

Frequency Protection (optional)

Frequency Elements
Quantity
Pick-up Values
f> or f< adjustable for each element
For f
= 50 Hz
N
For f
= 60 Hz
N
Times
Pickup times f>, f<
Dropout times f>, f<
Delay times T
The set times are pure delay times.
Note on dropout times:
Dropout was enforced by current = 0 A and voltage = 0 V.
Enforcing the dropout by means of a frequency change below the dropout threshold extends the dropout times.
Dropout Frequency
∆f = | pickup value – dropout value |
Operating Range
In voltage range
In frequency range
Tolerances
Frequencies f>, f< in specific range (f
Time delays T(f<, f>)
350
4, depending on setting effective on f< or f>
45.50 Hz to 54.50 Hz
55.50 Hz to 64.50 Hz
Approx. 85 ms
Approx. 30 ms
0.00 s to 600.00 s
Approx. 20 mHz
approx. 0.65 · U
25 Hz to 70 Hz
± 10 %)
15 mHz in range U
N
1 % of setting value or 10 ms
Increments 0.01 Hz
Increments 0.01 Hz
Increments 0.01 s
up to 230 V (phase-phase)
N
: 50 V to 230 V
LL
7SD610 Manual