Settings - Siemens siprotec 7SD610 User Manual

Differential protection
Hide thumbs Also See for siprotec 7SD610:
Table of Contents

Advertisement

2 Functions
may be present before the pole discrepancy supervision issues a three-pole trip com-
mand. This time must be clearly longer than the duration of a single-pole automatic
reclose cycle. The time should be less than the permissible duration of an unbalanced
load condition which is caused by the unsymmetrical position of the circuit breaker
poles. Conventional values are 2 s to 5 s.

2.13.3 Settings

The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr.
Parameter
3901
FCT BreakerFail
3902
I> BF
3903
1p-RETRIP (T1)
3904
T1-1pole
3905
T1-3pole
3906
T2
3907
T3-BkrDefective
3908
Trip BkrDefect.
3909
Chk BRK CONTACT
3912
3I0> BF
3921
End Flt. stage
3922
T-EndFault
3931
PoleDiscrepancy
3932
T-PoleDiscrep.
192
C
Setting Options
ON
OFF
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
NO
YES
0.00 .. 30.00 sec; ∞
0.00 .. 30.00 sec; ∞
0.00 .. 30.00 sec; ∞
0.00 .. 30.00 sec; ∞
NO
with T1-trip
with T2-trip
w/ T1/T2-trip
NO
YES
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
ON
OFF
0.00 .. 30.00 sec; ∞
ON
OFF
0.00 .. 30.00 sec; ∞
Default Setting
ON
Breaker Failure Protection
0.10 A
Pick-up threshold I>
0.50 A
YES
1pole retrip with stage T1
(local trip)
0.00 sec
T1, Delay after 1pole start
(local trip)
0.00 sec
T1, Delay after 3pole start
(local trip)
0.15 sec
T2, Delay of 2nd stage
(busbar trip)
0.00 sec
T3, Delay for start with de-
fective bkr.
NO
Trip output selection with
defective bkr
YES
Check Breaker contacts
0.10 A
Pick-up threshold 3I0>
0.50 A
OFF
End fault protection
2.00 sec
Trip delay of end fault pro-
tection
OFF
Pole Discrepancy supervi-
sion
2.00 sec
Trip delay with pole dis-
crepancy
Comments
7SD610 Manual
C53000-G1176-C145-4