Information List - Siemens siprotec 7SD610 User Manual

Differential protection
Hide thumbs Also See for siprotec 7SD610:
Table of Contents

Advertisement

2.13.4 Information List

No.
Information
1401
>BF on
1402
>BF off
1403
>BLOCK BkrFail
1415
>BF Start 3pole
1432
>BF release
1435
>BF Start L1
1436
>BF Start L2
1437
>BF Start L3
1439
>BF Start w/o I
1440
BkrFailON/offBI
1451
BkrFail OFF
1452
BkrFail BLOCK
1453
BkrFail ACTIVE
1461
BF Start
1472
BF T1-TRIP 1pL1
1473
BF T1-TRIP 1pL2
1474
BF T1-TRIP 1pL3
1476
BF T1-TRIP L123
1493
BF TRIP CBdefec
1494
BF T2-TRIP(bus)
1495
BF EndFlt TRIP
1496
BF CBdiscrSTART
1497
BF CBdiscr L1
1498
BF CBdiscr L2
1499
BF CBdiscr L3
1500
BF CBdiscr TRIP
7SD610 Manual
C53000-G1176-C145-4
Type of In-
formation
SP
>BF: Switch on breaker fail protection
SP
>BF: Switch off breaker fail protection
SP
>BLOCK Breaker failure
SP
>BF: External start 3pole
SP
>BF: External release
SP
>BF: External start L1
SP
>BF: External start L2
SP
>BF: External start L3
SP
>BF: External start 3pole (w/o current)
IntSP
Breaker failure prot. ON/OFF via BI
OUT
Breaker failure is switched OFF
OUT
Breaker failure is BLOCKED
OUT
Breaker failure is ACTIVE
OUT
Breaker failure protection started
OUT
BF Trip T1 (local trip) - only phase L1
OUT
BF Trip T1 (local trip) - only phase L2
OUT
BF Trip T1 (local trip) - only phase L3
OUT
BF Trip T1 (local trip) - 3pole
OUT
BF Trip in case of defective CB
OUT
BF Trip T2 (busbar trip)
OUT
BF Trip End fault stage
OUT
BF Pole discrepancy pickup
OUT
BF Pole discrepancy pickup L1
OUT
BF Pole discrepancy pickup L2
OUT
BF Pole discrepancy pickup L3
OUT
BF Pole discrepancy Trip
2.13 Circuit Breaker Failure Protection