2.16.3.4 Setting Notes

Fault Messages
Pickup of a new protective function generally turns off any previously lit LEDs, so that
only the latest fault is displayed at any time. It can be selected whether the stored LED
displays and the spontaneous indications on the display appear upon renewed pickup,
or only after a renewed trip signal is issued. In order to enter the desired type of dis-
play, select the submenu Device in the SETTINGS menu. At address 610
FltDisp.LED/LCD the two alternatives Target on PU and Target on TRIP („No
trip - no flag") are offered.
After startup of a device featuring a 4-line display, measured values are displayed by
default. Use the arrow keys on the device front to select the different represenations
of the measured values for the so-called default display. The start page of the default
display, which is displayed by default after startup of the device, can be selected via
parameter 640 Start image DD. The available representation types for the mea-
sured values are listed in the appendix .

2.16.3.5 Settings

Addr.
Parameter
610
FltDisp.LED/LCD
640
Start image DD

2.16.3.6 Information List

No.
Information
-
Test mode
-
DataStop
-
UnlockDT
-
Reset LED
-
SynchClock
-
>Light on
-
HWTestMod
-
Distur.CFC
-
Brk OPENED
-
FdrEARTHED
3
>Time Synch
5
>Reset LED
11
>Annunc. 1
12
>Annunc. 2
13
>Annunc. 3
14
>Annunc. 4
7SD610 Manual
C53000-G1176-C145-4
Setting Options
Target on PU
Target on TRIP
image 1
image 2
image 3
image 4
image 5
image 6
Type of In-
formation
IntSP
Test mode
IntSP
Stop data transmission
IntSP
Unlock data transmission via BI
IntSP
Reset LED
IntSP_Ev
Clock Synchronization
SP
>Back Light on
IntSP
Hardware Test Mode
OUT
Disturbance CFC
IntSP
Breaker OPENED
IntSP
Feeder EARTHED
SP
>Synchronize Internal Real Time Clock
SP
>Reset LED
SP
>User defined annunciation 1
SP
>User defined annunciation 2
SP
>User defined annunciation 3
SP
>User defined annunciation 4
2.16 Function Control and Circuit Breaker Test
Default Setting
Target on PU
Fault Display on LED / LCD
image 1
Start image Default Display
Comments