No.
Description
1002
Number of breaker TRIP com-
mands L2 (TripNo L2=)
1003
Number of breaker TRIP com-
mands L3 (TripNo L3=)
1027
Accumulation of interrupted
current L1 (Σ IL1
=)
1028
Accumulation of interrupted
current L2 (Σ IL2
=)
1029
Accumulation of interrupted
current L3 (Σ IL3
=)
1030
Max. fault current Phase L1 (Max
IL1 =)
1031
Max. fault current Phase L2 (Max
IL2 =)
1032
Max. fault current Phase L3 (Max
IL3 =)
1401
>BF: Switch on breaker fail pro-
tection (>BF on)
1402
>BF: Switch off breaker fail pro-
tection (>BF off)
1403
>BLOCK Breaker failure
(>BLOCK BkrFail)
1415
>BF: External start 3pole (>BF
Start 3pole)
1432
>BF: External release (>BF re-
lease)
1435
>BF: External start L1 (>BF Start
L1)
1436
>BF: External start L2 (>BF Start
L2)
1437
>BF: External start L3 (>BF Start
L3)
1439
>BF: External start 3pole (w/o
current) (>BF Start w/o I)
1440
Breaker failure prot. ON/OFF via
BI (BkrFailON/offBI)
1451
Breaker failure is switched OFF
(BkrFail OFF)
1452
Breaker failure is BLOCKED
(BkrFail BLOCK)
1453
Breaker failure is ACTIVE (Bkr-
Fail ACTIVE)
1461
Breaker failure protection started
(BF Start)
1472
BF Trip T1 (local trip) - only
phase L1 (BF T1-TRIP 1pL1)
1473
BF Trip T1 (local trip) - only
phase L2 (BF T1-TRIP 1pL2)
1474
BF Trip T1 (local trip) - only
phase L3 (BF T1-TRIP 1pL3)
1476
BF Trip T1 (local trip) - 3pole (BF
T1-TRIP L123)
1493
BF Trip in case of defective CB
(BF TRIP CBdefec)
1494
BF Trip T2 (busbar trip) (BF T2-
TRIP(bus))
7SD610 Manual
C53000-G1176-C145-4
Function
Type
of In-
for-
matio
n
Statistics
VI
Statistics
VI
Statistics
VI
Statistics
VI
Statistics
VI
Statistics
VI
Statistics
VI
Statistics
VI
Breaker Failure
SP
*
Breaker Failure
SP
*
Breaker Failure
SP
ON
OFF
Breaker Failure
SP
ON
OFF
Breaker Failure
SP
ON
OFF
Breaker Failure
SP
ON
OFF
Breaker Failure
SP
ON
OFF
Breaker Failure
SP
ON
OFF
Breaker Failure
SP
ON
OFF
Breaker Failure
IntSP
ON
OFF
Breaker Failure
OUT
ON
OFF
Breaker Failure
OUT
ON
OFF
Breaker Failure
OUT
*
Breaker Failure
OUT
*
Breaker Failure
OUT
*
Breaker Failure
OUT
*
Breaker Failure
OUT
*
Breaker Failure
OUT
*
Breaker Failure
OUT
*
Breaker Failure
OUT
*
Log Buffers
Configurable in Matrix
*
*
LED BI
*
*
LED BI
*
*
LED BI
*
*
LED BI
*
*
LED BI
*
*
LED BI
*
*
LED BI
*
*
LED BI
*
*
LED BI
*
*
LED
*
*
LED
ON
*
LED
OFF
*
*
LED
ON
*
LED
OFF
ON
*
LED
ON
*
LED
ON
*
LED
ON
*
LED
ON
*
LED
ON
*
LED
A.8 Information List
IEC 60870-5-103
BO
BO
BO
166
103
1
Yes
BO
BO
BO
BO
BO
BO
BO
BO
166
151
1
Yes
BO
166
152
1
Yes
BO
166
153
1
Yes
BO
166
161
2
Yes
BO
BO
BO
BO
BO
BO
192
85
2
No
399