2.15.2 Trip Circuit Supervision

The line protection 7SD610 is equipped with an integrated trip circuit supervision func-
tion. Depending on the number of available binary inputs (not connected to a common
potential), supervision with one or two binary inputs can be selected. If the routing of
the binary inputs required for this does not comply with the selected supervision mode,
an alarm is given („TripC1 ProgFAIL ...", with identification of the non-compliant cir-
cuit). When using two binary inputs, malfunctions in the trip circuit can be detected
under all circuit breaker conditions. When only one binary input is used, malfunctions
in the circuit breaker itself cannot be detected. If single-pole tripping is possible, a sep-
arate trip circuit supervision can be implemented for each circuit breaker pole provided
the required binary inputs are available.

2.15.2.1 Function Description

Supervision with
When using two binary inputs, these are connected according to Figure 2-90 parallel
Two Binary Inputs
to the associated trip contact on one side, and parallel to the circuit breaker auxiliary
contacts on the other.
A precondition for the use of the trip circuit monitoring is that the control voltage for the
circuit breaker is higher than the total of the minimum voltages drops at the two binary
inputs (U
itoring function can only be used with a system control voltage of over 38 V.
7SD610 Manual
C53000-G1176-C145-4
Type of In-
formation
OUT
Failure: Voltage summation Phase-Earth
OUT
Failure: Voltage Balance
OUT
Failure: Voltage absent
OUT
VT Fuse Failure (alarm >10s)
OUT
VT Fuse Failure (alarm instantaneous)
OUT
Failure: Phase Sequence
OUT
Fuse Fail Monitor is switched OFF
OUT
Measurement Supervision is switched OFF
OUT
Alarm: Current summation supervision
OUT
Alarm: Broken current-wire detected L1
OUT
Alarm: Broken current-wire detected L2
OUT
Alarm: Broken current-wire detected L3
OUT
Broken wire supervision is switched OFF
OUT
Current summation superv is switched OFF
OUT
Broken current-wire at other end L1
OUT
Broken current-wire at other end L2
OUT
Broken current-wire at other end L3
> 2·U
). Since at least 19 V are needed for each binary input, the mon-
Ctrl
BImin
2.15 Monitoring Functions