Information List - Siemens siprotec 7SD610 User Manual

Differential protection
Hide thumbs Also See for siprotec 7SD610:
Table of Contents

Advertisement

Addr.
Parameter
3486
4.AR Tdead 1Flt
3487
4.AR Tdead 2Flt
3488
4.AR Tdead 3Flt
3489
4.AR Tdead1Trip
3490
4.AR Tdead3Trip
3491
4.AR: Tdead EV.
3492
4.AR: CB? CLOSE
3493
4.AR SynRequest

2.10.4 Information List

No.
Information
127
AR ON/OFF
2701
>AR on
2702
>AR off
2703
>AR block
2711
>AR Start
2712
>Trip L1 AR
2713
>Trip L2 AR
2714
>Trip L3 AR
2715
>Trip 1pole AR
2716
>Trip 3pole AR
2727
>AR RemoteClose
2731
>Sync.release
2737
>BLOCK 1pole AR
2738
>BLOCK 3pole AR
2739
>BLK 1phase AR
2740
>BLK 2phase AR
2741
>BLK 3phase AR
2742
>BLK 1.AR-cycle
2743
>BLK 2.AR-cycle
2744
>BLK 3.AR-cycle
2745
>BLK 4.-n. AR
2746
>Trip for AR
2747
>Pickup L1 AR
2748
>Pickup L2 AR
2749
>Pickup L3 AR
2750
>Pickup 1ph AR
2751
>Pickup 2ph AR
2752
>Pickup 3ph AR
2781
AR off
7SD610 Manual
C53000-G1176-C145-4
Setting Options
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec; ∞
0.01 .. 1800.00 sec
YES
NO
YES
NO
Type of In-
formation
IntSP
Auto Reclose ON/OFF (via system port)
SP
>AR: Switch on auto-reclose function
SP
>AR: Switch off auto-reclose function
SP
>AR: Block auto-reclose function
SP
>External start of internal Auto reclose
SP
>AR: External trip L1 for AR start
SP
>AR: External trip L2 for AR start
SP
>AR: External trip L3 for AR start
SP
>AR: External 1pole trip for AR start
SP
>AR: External 3pole trip for AR start
SP
>AR: Remote Close signal
SP
>AR: Sync. release from ext. sync.-check
SP
>AR: Block 1pole AR-cycle
SP
>AR: Block 3pole AR-cycle
SP
>AR: Block 1phase-fault AR-cycle
SP
>AR: Block 2phase-fault AR-cycle
SP
>AR: Block 3phase-fault AR-cycle
SP
>AR: Block 1st AR-cycle
SP
>AR: Block 2nd AR-cycle
SP
>AR: Block 3rd AR-cycle
SP
>AR: Block 4th and higher AR-cycles
SP
>AR: External Trip for AR start
SP
>AR: External pickup L1 for AR start
SP
>AR: External pickup L2 for AR start
SP
>AR: External pickup L3 for AR start
SP
>AR: External pickup 1phase for AR start
SP
>AR: External pickup 2phase for AR start
SP
>AR: External pickup 3phase for AR start
OUT
AR: Auto-reclose is switched off
2.10 Automatic Reclosure Function (optional)
Default Setting
1.20 sec
Dead time after 1phase faults
1.20 sec
Dead time after 2phase faults
0.50 sec
Dead time after 3phase faults
∞ sec
Dead time after 1pole trip
0.50 sec
Dead time after 3pole trip
1.20 sec
Dead time after evolving fault
NO
CB ready interrogation before re-
closing
NO
Request for synchro-check after
3pole AR
Comments