Siemens siprotec 7SD610 User Manual page 297

Differential protection
Hide thumbs Also See for siprotec 7SD610:
Table of Contents

Advertisement

Figure 3-17
Changing the oper-
To change the operating state of a hardware component, click on the associated
ating state
switching field in the Scheduled column.
Before executing the first change of the operating state the password No. 6 will be re-
quested (if activated during configuration). After entry of the correct password a con-
dition change will be executed. Further state changes remain enabled until the dialog
box is closed.
Test of the Output
Each individual output relay can be energized allowing a check of the wiring between
Relays
the output relay of the 7SD610 and the plant, without having to generate the message
that is assigned to the relay. As soon as the first change of state for any of the output
relays is initiated, all output relays are separated from the internal device functions,
and can only be operated by the hardware test function. This means, that e.g. a TRIP
command coming from a protection function or a control command from the operator
panel to an output relay cannot be executed.
Proceed as follows in order to check the output relay:
• Make sure that the switching operations caused by the output relays can be execut-
• Each output relay must be tested via the corresponding Scheduled field of the
• Finish the testing (see margin heading below „Exiting the Procedure"), so that
Test of the Binary
To test the wiring between the plant and the binary inputs of the 7SD610 the condition
Inputs
in the system which initiates the binary input must be generated and the response of
the device checked.
To do so, open the dialog box Hardware Test again to view the physical position of
the binary input. The password is not yet required.
7SD610 Manual
C53000-G1176-C145-4
Test of the Binary Inputs and Outputs — Example
ed without any danger (see above under DANGER!).
dialog box.
during further testings no unwanted switchings are initiated.
3.3 Commissioning