1. System Times
1. System Times
1 . 3
1 . 3
S e l f T e s t ( c o n t i n u e d )
S e l f T e s t ( c o n t i n u e d )
1.3.3 Time of Day for Self Test
TIME HH:MM
__:__ AM 1=PM
Select the time of day the Self Test report will be transmitted to the central station.
(see 1.3.4-Test Rpt Code / 1.3.5-Ab Test Rpt Code / 1.3.6-Telco / 3.8.3-Rcvr Routing).
1.3.4 Self Test Code
SELF TEST CODE
code NO
Select the Self Test report code that will be transmitted to the central station via
both digital and radio (requires additional radio hardware).
(see SIA-Contact ID-Hex charts on pg 42 & 43).
1.3.5 Abnormal Test Code
ABNORMAL CODE
code NO
Select the Abnormal Code that will be transmitted to the central station when a zone(s)
designated as a Fire Zone and/or the 2-wire smoke detector zone has gone into an alarm
condition that has not been restored to a normal condition once the Self Test Time arrives.
(see SIA-Contact ID-Hex charts on pg 42 & 43).
1.3.6 Report Self Test on Telco
TELCO REPORT
YES
0=NO 1=YES
Enable this option to transmit the Self Test report code via the telephone line(s).
1.3.7 Report Self Test on Radio
RADIO REPORT
NO
0=NO 1=YES
Enable this option to transmit the Self Test report code via Varitech long range radio.
(additional hardware required).
Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839
Selections: 12:00am - 11:59pm
Default: No time
Selections: 01-FF / Contact ID / SIA
Default: No report
Selections: 01-FF / Contact ID / SIA
Default: No Report
Selections: Yes / No
Default: Yes
Selections: Yes / No
Default: No
SMDC-16 Program Manual
1. System Times
1. Delay Times
1. Pre-Alarm
2. Entry Delay
3. Exit Delay
4. AC Fail Delay
5. AC Fail Display
2. Cutoff Times
1. Bell 1
2. Bell 2
3. Relay 1
4. Relay 2
5. PGM 1
6. PGM 2
7. PGM 3
8. Listen - In
3. Self Test
1. Daily
2. Weekly
3. Time of Day
4. Self Test Code
5. Abnormal test Code
6. Telco Test Report
7. Radio Test Report
4. Real Time Clock
1. Time Clock
1. Set Date
2. Set Time
2. Set by User