U.L. Information Addendum
• The exit delay time shall not exceed 60 seconds. (section 1.1.3)
• The entry delay time shall not exceed 45 seconds. (section 1.1.2)
• The sounder cutoff time shall not be less than 4 minutes. (section 1.2)
• The AC power failure report time shall not be more than 360 minutes. (section 1.1.4)
• The delay before Dial time shall be 0 seconds. (section 3.5.4)
• "Normally Open" loop type is only suitable for Grade B, Household Burglary. (section 2.1.1)
• "Normally Closed" loop type is only suitable for Grade B, Household Burglary. (section 2.1.1)
• "Normally Open/Normally Closed" loop type is only suitable for Grade A, Household Burglary and Commercial
Burglary. (section 2.1.1)
• The dial attempts shall not be less than 5 and more than 10. (section 3.4)
• If fire alarm verification feature is used, the "Fire Alarm Verify" feature shall be enabled. (section 4.6.5)
• The 'alarm verify' noted in 2.1.9 should not be used in any UL listed application. (section 2.1.9)
• DACT and BELL shall be tested every 24 hours for Commercial Fire. (section 1.3 & 6.4.7)
• For Fire bell to Ring in Temporal Pattern, the following settings must be entered:
• The SMDC-WX (wireless features) has not been investigated for use in UL Listed Fire Applications
or UL Listed Burglar Applications. (section 2.7)
Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual
1. Zone Type must be set to Fire Zone (section 2.1.1).
2. Bell 1 must be set to Yes (section 2.8.1).
3. Bell 1 Pulse must be set to Yes (section 2.8.2).
4. Temporal Fire must be set to Yes (section 4.9).