PROGRAMMING MANUAL
SMDC-16 Digital Control Communicator
and
SMPC-32 Personal Control
Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839
SMDC-16 Program Manual
3440-0252 A4

Advertisement

Table of Contents
loading

Summary of Contents for Optex SMDC-16

  • Page 1 SMDC-16 SMDC-16 PROGRAMMING MANUAL SMDC-16 Digital Control Communicator SMPC-32 Personal Control Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 2: Table Of Contents

    Quick Reference chart of program locations and receiver routing SIA Information Quick reference chart - additional report code options Zone Type Quick reference chart Description UL Addendum UL information Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 3 I n t r o d u c t i o n & P r o g r a m H i n t s All programming for the OPTEX INC. SMDC may be accomplished through the SMPC-32 Personal Control Keypad or from the DOS –...
  • Page 4 5. Alarm Verify. 4. Number of Shunt Alm 1. Partition 1 6. Outputs 5. Shunt Period 2. Partition 2 1. Bell 1 Output Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 5 I n s t a l l e r P r o g r a m M e n u I n s t a l l e r P r o g r a m M e n u Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual...
  • Page 6: System Times

    1. Pre-Alarm and Real Time Clock. 2. Entry Delay 3. Exit Delay 4. AC Fail Delay 5. AC Fail Display Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 2. Cutoff Times...
  • Page 7 10 MINUTES Default: 10 minutes. Select the amount of time in minutes alarm output voltage will be present for Bell 2 output. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 8 Select the day of the week for transmission of the self test code after weekly test has been enabled. (see 1.3.4-Test Rpt Code / 1.3.5-Ab Test Rpt Code / 3.8.3-Rcvr Routing). Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual...
  • Page 9 0=NO 1=YES Default: No Enable this option to transmit the Self Test report code via Varitech long range radio. (additional hardware required). Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 10 Selections: 0=No 1=Yes 0=NO 1=YES Default: No Enable this option to allow the internal clock to automatically compensate for daylight savings time. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 11: Zone Configuration

    (see Contact ID / SIA note in 2.1.3). Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 12 3. Cross Zone Timer (see user manual for PIN authorization levels). 4. # of Shunt Alarms 5. Shunt Period 6. # of Expander Bds. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 13 N o t e : 2.1.8.1 Bell 1 output must be programmed as YES for this Pulse Bell option to function. N o t e 5. Shunt Period 6. # of Expander Bds. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 14 1. Zone A 2. Zone B 3. Cross Zone Timer 4. # of Shunt Alarms 5. Shunt Period 6. # of Expander Bds. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 15 N o t e : The zone description will not display if Group Arming is enabled. N o t e 3. Cross Zone Timer 4. # of Shunt Alarms 5. Shunt Period 6. # of Expander Bds. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 16 N o t e : 2.1.8.1 Bell 2 output must be programmed as YES for this Pulse Bell option to function. N o t e 3. Cross Zone Timer 4. # of Shunt Alarms 5. Shunt Period 6. # of Expander Bds. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 17 Select the applicable zone that will be used for Zone A of Cross Zone Pair 2. 3. Cross Zone Timer 4. # of Shunt Alarms 5. Shunt Period 6. # of Expander Bds. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 18 1. Zone A 2. Zone B 3. Cross Zone Timer 4. # of Shunt Alarms 5. Shunt Period 6. # of Expander Bds. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 19 1. Zone A 2. Zone B 3. Cross Zone Timer 4. # of Shunt Alarms 5. Shunt Period 6. # of Expander Bds. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 20 94 = { 23 = W 47 = u 71 = “ 95 = } 24 = X 48 = v 72 = # Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 21 Trouble report code transmitted if programmed on all zone types. Disarmed - Trouble report code transmitted if programmed on zone type 6 (24 hr)- 7 (fire) only. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual...
  • Page 22: Receiver

    Select the account number to be transmitted for zones 25-32. 3.1.1.2.1.5 Zones 33-40 Select the account number to be transmitted for zones 33-40. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 23 14. Ademco Contact ID The programming sequence for Receiver 2 is identical to Receiver 1. Program the necessary information as required for Receiver 2. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 24 Enable this option to energize PGM 1 when the SMDC has detected a telco line fault condition. (see 1.2 Cutoff Times). Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 24 of 59...
  • Page 25 Enter the period of time the phone line must be faulted before the SMDC will panel will generate a TLM fault condition. (see 3.7 TLM Report codes). Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 26 N o t e : You may only select receiver options 1 to 4 for alarms. N o t e : (see page 27 for additional information regarding routing). Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 27 Enable this option for the first radio signal to be transmitted to the central station prior to a digital dialing attempt. 3.9.4 Radio Account Numbers Do not program unless Optex Radio will be installed. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 27 of 59...
  • Page 28 3.8.3. Zone Trouble 2.3.2 3.8.1 Legend 3.8.1 = Alarm Codes / 3.8.2 = Open\Close Codes 3.8.3 = System Codes Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 28 of 59...
  • Page 29: System Options

    8. PGM / INP Functions 1. PGM 1 Function 2. PGM 2 Function 3. PGM 3 Function 4. INP-1 Function Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 29 of 59...
  • Page 30 No = Alarm Reported / alarm outputs activated 3. PGM 3 Function 9. Garage No = No Activation (no report) 4. INP-1 Function Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 30 of 59...
  • Page 31 N o t e : The SMDC control/communicator is able to log 512 total events. N o t e 2. PGM 2 Function 3. PGM 3 Function 4. INP-1 Function Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 31 of 59...
  • Page 32 (see 5.3.3 Unauthorized User report code). 1. PGM 1 Function 2. PGM 2 Function 3. PGM 3 Function 4. INP-1 Function Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 32 of 59...
  • Page 33 Enable this option to activate Bell 1 output when the Emergency keys have been activated. 4. INP-1 Function (see 2.2.1-Cutoff Times / 4.5.1-Emergency Enable). Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 34 8. PGM / INP Functions 1. PGM 1 Function 2. PGM 2 Function 3. PGM 3 Function 4. INP-1 Function Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 34 of 59...
  • Page 35 (see 1.2 Cut Off Times). 2. PGM 2 Function 3. PGM 3 Function 4. INP-1 Function Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 35 of 59...
  • Page 36 4. INP-1 Function Default: No Select one of the options from the PGM list on page 37. (see wiring diagram). Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 36 of 59...
  • Page 37: Temporal Fire

    3. PGM 3 Function (see 1.2 Cut Off Times) 4. INP-1 Function Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 37 of 59...
  • Page 38: Input Options

    N o t e : The SMDC also has the provision for a monetary input for arming/disarming a non partition SMDC. (see wiring diagram). Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual...
  • Page 39: Report Codes

    SMDC detects a trouble condition on the Bell 1 circuit. (see Wiring diagram / 3.8.3-Rcvr Routing / SIA-Contact ID-Hex chart on page 42 & 43). Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 40 (see 1.2 Exit Delay Time / 3.8.3-Rcvr Routing / SIA-Contact ID-Hex chart on page 42 & 43). Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 41 PIN numbers have been entered at a keypad (see 4.9-Threshold of Bad Codes / 3.8.3-Rcvr Routing / SIA-Contact ID-Hex chart on page 42 & 43). Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 42 SMDC has been armed in the Stay or Instant mode. (see 3.8.3-Rcvr Routing / SIA-Contact ID-Hex chart on page 42 & 43 / User Manual). Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 43 Hexadecimal Letter Keypad Button AWAY STAY INSTANT MEMORY PROGRAM MONITOR Depress the appropriate keypad button for the desired hexadecimal character. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 43 of 59...
  • Page 44 Prog. Prog. 2.8. Zone Trbl 2.2. Prog = Programmable Y/N no = not available on = cannot be disabled Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 44 of 59...
  • Page 45: Pin Numbers

    4. User Report Codes E x t r e m e W a r n i n g : The panel must returned to Optex Inc. if this entry is unknown E x t r e m e W a r n i n g 1.
  • Page 46 W A R N I N G : over write what has been programmed in 6.4.3 User Open code and 6.4.4 User Close code. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 47: Review Pin

    USER 1 PIN Selections: No programming 1234 Default: 1234 This option allows you to review user 1 PIN. (No programming allowed). Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 47 of 59...
  • Page 48 N o t e : FFFF (monitor 4 times) will delete the Access ID number and download access will be denied. N o t e Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 49 N o t e : Bypass report will be transmitted (if programmed) at the time of arming. N o t e Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 49 of 59...
  • Page 50 After CLEAR has been pressed, the days of the week (1-7) will be scrolling. Select the the day that you wish to program by pressing the corresponding number. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 51 Select the time of day the Open time is to begin. N o t e : To delete the time press Reset. N o t e : Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 51 of 59...
  • Page 52 Select the number of days of the holiday 8.2.3.3. View Holiday This option is for viewing purposes only and therefore no programming is allowed. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 52 of 59...
  • Page 53 1 OPEN START Selections __:__ AM 1=PM Default: No Time Select the Open Start time for Temporary Schedule 1. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 53 of 59...
  • Page 54 Enable this option to allow the SMPCs to emit a tone 10 minutes prior to the end of the close window for Schedule 1 only. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 55 NUMBER OF GRPS Selections: 1 - 8 Default: 1 Enter the total number of groups or partitions that will be needed. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 55 of 59...
  • Page 56 W a r n i n g : (see 6.4-Open-Close Report Codes / SIA-Contact ID-Hex chart on page 42 & 43). Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 56 of 59...
  • Page 57 E x a m p l e : group numbers 2-3-5-7 - Press 2-3-5-7. E x a m p l e Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 57 of 59...
  • Page 58 Select this option to allow the System report codes to be sent to the paging service after the digital communication signal has been kissed off at the central station. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 59 This options determines the type of events the alarm panel will be transmitting to the on site printer. Your options are: 01. All occurrences. 02. Alarm occurrences. 03. Open and Close occurrences. Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4 59 of 59...
  • Page 60 • The SMDC-WX (wireless features) has not been investigated for use in UL Listed Fire Applications or UL Listed Burglar Applications. (section 2.7) Optex Inc. - 1845 W 205th St. - Torrance, Ca. 90501 - 800-966-7839 SMDC-16 Program Manual 3440-0252 A4...
  • Page 61 Filename: 252_A4.DOC Directory: C:\WINDOWS\Desktop\SMDC PDF\Prg Man Template: C:\Program Files\Microsoft Office\Templates\Normal.dot Title: Subject: Author: Unknown Keywords: Comments: Creation Date: 01/25/00 15:16 Change Number: Last Saved On: 01/26/00 09:56 Last Saved By: Joshua Total Editing Time: 94 Minutes Last Printed On: 01/26/00 10:50 As of Last Complete Printing Number of Pages: Number of Words:...