Diagnostics and Troubleshoo...
Number
Description
311
Switch. freq. limit
312
CT range
314
Auto CT interrupt
315
Auto CT error
316
CT location error
317
CT polarity error
318
CT ratio error
Table 7.2 Alarm/Warning Code List
A trip is the action when an alarm has appeared. The trip disables the active filter and can be reset by pressing [Reset] or
resetting via a digital input (parameter group 5-1* Digital Inputs [1] Reset). The original event that caused an alarm cannot
damage the active filter or cause dangerous conditions. A trip lock is an action when an alarm occurs, which may cause
damage to active filter or connected parts. A trip lock situation can only be reset by a power cycling.
Warning
Alarm
Trip locked
Table 7.3 LED Indicator Lights
MG16I302
Operating Instructions
Warning
X
X
X
Yellow
Flashing red
Yellow and red
Danfoss A/S © 04/2015 All rights reserved.
Alarm/Trip
Alarm/Trip Lock
X
X
X
X
Parameter Reference
7
77
7