Asynchronous Motor Set-Up; Permanent Magnet Motor Set-Up - Danfoss VLT FC 102 Operating Instructions Manual

Hvac drive low harmonic drive
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Commissioning
10.
Make the application-specific settings in the
following parameters:
10a
Parameter 3-02 Minimum Reference.
10b
Parameter 3-03 Maximum Reference.
10c
Parameter 3-41 Ramp 1 Ramp Up Time.
10d
Parameter 3-42 Ramp 1 Ramp Down
Time.
10e
Parameter 3-13 Reference Site. Linked to
Hand/Auto Local Remote.

5.4.4 Asynchronous Motor Set-up

Enter the following motor data. The information can be
found on the motor nameplate.
1.
Parameter 1-20 Motor Power [kW] or
parameter 1-21 Motor Power [HP].
2.
Parameter 1-22 Motor Voltage.
3.
Parameter 1-23 Motor Frequency.
4.
Parameter 1-24 Motor Current.
5.
Parameter 1-25 Motor Nominal Speed.
When running in flux mode, or for optimum performance
in VVC
+
mode, extra motor data is required to set up the
following parameters. The data can be found in the motor
datasheet (this data is typically not available on the motor
nameplate). Run a complete AMA using
parameter 1-29 Automatic Motor Adaptation (AMA) [1]
Enable Complete AMA or enter the parameters manually.
Parameter 1-36 Iron Loss Resistance (Rfe) is always entered
manually.
1.
Parameter 1-30 Stator Resistance (Rs).
2.
Parameter 1-31 Rotor Resistance (Rr).
3.
Parameter 1-33 Stator Leakage Reactance (X1).
4.
Parameter 1-34 Rotor Leakage Reactance (X2).
5.
Parameter 1-35 Main Reactance (Xh).
6.
Parameter 1-36 Iron Loss Resistance (Rfe).
Application-specific adjustment when running VVC
+
VVC
is the most robust control mode. In most situations,
it provides optimum performance without further
adjustments. Run a complete AMA for best performance.
Application-specific adjustment when running Flux
Flux mode is the preferred control mode for optimum
shaft performance in dynamic applications. Perform an
AMA since this control mode requires precise motor data.
Depending on the application, further adjustments may be
required.
See Table 5.7 for application-related recommendations.
MG16I302
Operating Instructions
Application
Low-inertia applications
High-inertia applications
High load at low speed
No-load application
Flux sensorless only
Table 5.7 Recommendations for Flux Applications

5.4.5 Permanent Magnet Motor Set-up

NOTICE
+
Only use permanent magnet (PM) motor with fans and
pumps.
Initial programming steps
1.
2.
Danfoss A/S © 04/2015 All rights reserved.
Settings
Keep calculated values.
Parameter 1-66 Min. Current at Low
Speed.
Increase current to a value between
default and maximum depending on
the application.
Set ramp times matching the
application. Too fast ramp up causes
an overcurrent or overtorque. Too
fast ramp down causes an
overvoltage trip.
Parameter 1-66 Min. Current at Low
Speed.
Increase current to a value between
default and maximum depending on
the application.
Adjust parameter 1-18 Min. Current at
No Load to achieve smoother motor
operation by reducing torque ripple
and vibration.
Adjust parameter 1-53 Model Shift
Frequency.
Example 1: If the motor oscillates at
5 Hz and dynamics performance is
required at 15 Hz, set
parameter 1-53 Model Shift Frequency
to 10 Hz.
Example 2: If the application
involves dynamic load changes at
low speed, reduce
parameter 1-53 Model Shift Frequency.
Observe the motor behaviour to
make sure that the model shift
frequency is not reduced too much.
Symptoms of inappropriate model
shift frequency are motor oscillations
or frequency converter tripping.
Activate PM motor operation
parameter 1-10 Motor Construction, select [1] PM,
non-salient SPM.
Set parameter 0-02 Motor Speed Unit to [0] RPM.
5
5
59

Advertisement

Table of Contents
loading

Table of Contents