Troubleshooting
Remove the power from the frequency converter
and check motor phase V.
ALARM 32, Motor phase W missing
Motor phase W between the frequency converter and the
motor is missing.
Troubleshooting
Remove the power from the frequency converter
and check motor phase W.
ALARM 33, Inrush fault
Too many power-ups have occurred within a short time
period.
Troubleshooting
Let the unit cool to operating temperature.
WARNING/ALARM 34, Fieldbus communication fault
The fieldbus on the communication option card is not
working.
WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage to
the frequency converter is lost and parameter 14-10 Mains
Failure is not set to option [0] No Function. Check the fuses
to the frequency converter and mains supply to the unit.
ALARM 38, Internal fault
When an internal fault occurs, a code number defined in
Table 7.1 is displayed.
Troubleshooting
Cycle the power.
Check that the option is properly installed.
Check for loose or missing wiring.
It may be necessary to contact Danfoss Service or the
supplier. Note the code number for further troubleshooting
directions.
Number
Text
0
The serial port cannot be initialised. Contact your
Danfoss supplier or Danfoss Service.
256–258
The power EEPROM data is defective or too old.
512
The control board EEPROM data is defective or too
old.
513
Communication time-out reading EEPROM data
514
Communication time-out reading EEPROM data
515
Application-oriented control cannot recognise the
EEPROM data.
516
Cannot write to the EEPROM because a write
command is in progress.
517
The write command is under time-out.
518
Failure in the EEPROM.
519
Missing or invalid barcode data in EEPROM.
783
Parameter value outside of minimum/maximum
limits.
1024–1279 A CAN telegram could not be sent.
1281
Digital signal processor flash time-out.
MG16I302
Operating Instructions
Number
1282
1283
1284
1299
1300
1301
1302
1315
1316
1317
1318
1379
1380
1381
1382
1536
1792
2049
2064–2072 H081x: Option in slot x has restarted.
2080–2088 H082x: Option in slot x has issued a power-up
2096–2104 H983x: Option in slot x has issued a legal power-
2304
2305
2314
2315
2316
2324
2325
2326
2327
2330
2561
Danfoss A/S © 04/2015 All rights reserved.
Text
Power micro software version mismatch.
Power EEPROM data version mismatch.
Cannot read digital signal processor software
version.
The option software in slot A is too old.
The option software in slot B is too old.
The option software in slot C0 is too old.
The option software in slot C1 is too old.
The option software in slot A is not supported (not
allowed).
The option software in slot B is not supported (not
allowed).
The option software in slot C0 is not supported
(not allowed).
The option software in slot C1 is not supported
(not allowed).
Option A did not respond when calculating the
platform version
Option B did not respond when calculating the
platform version.
Option C0 did not respond when calculating the
platform version.
Option C1 did not respond when calculating the
platform version.
An exception in the application-oriented control is
registered. The debug information is written on
the LCP.
DSP Watch Dog is active. Debugging of power part
data, motor-oriented control data not transferred
correctly.
Power data restarted.
wait.
up wait.
Could not read any data from the power EEPROM.
Missing software version from the power unit.
Missing power unit data from the power unit.
Missing software version from the power unit.
Missing lo_statepage from the power unit.
The power card configuration is determined to be
incorrect at power-up.
A power card has stopped communicating while
mains power is applied.
The power card configuration is determined to be
incorrect after the delay for power cards to
register.
Too many power card locations have been
registered as present.
The power size information between the power
cards does not match.
No communication from DSP to ATACD.