Diagnostics and Troubleshoo...
ALARM 246, Power card supply
This alarm is only for enclosure size F frequency converters.
It is equivalent to Alarm 46. The report value in the alarm
log indicates which power module generated the alarm:
1 = Left most inverter module.
2 = Middle inverter module in enclosure sizes F12
or F13.
2 = Right inverter module in enclosure sizes F10
or F11.
2 = Second frequency converter from the left
inverter module in enclosure size F14 or F15.
3 = Right inverter module in enclosure sizes F12
or F13.
3 = Third from the left inverter module in
enclosure size F14 or F15.
4 = Far right inverter module in enclosure size
F14 or F15.
5 = Rectifier module.
6 = Right rectifier module in enclosure size F14 or
F15.
ALARM 247, Power card temperature
This alarm is only for enclosure size F frequency converters.
It is equivalent to Alarm 69. The report value in the alarm
log indicates which power module generated the alarm:
1 = Left most inverter module.
2 = Middle inverter module in enclosure sizes F12
or F13.
2 = Right inverter module in enclosure sizes F10
or F11.
2 = Second frequency converter from the left
inverter module in enclosure size F14 or F15.
3 = Right inverter module in enclosure sizes F12
or F13.
3 = Third from the left inverter module in
enclosure size F14 or F15.
4 = Far right inverter module in enclosure size
F14 or F15.
5 = Rectifier module.
6 = Right rectifier module in enclosure size F14 or
F15.
ALARM 248, Illegal power section configuration
This alarm is only for enclosure size F frequency converters.
It is equivalent to Alarm 79. The report value in the alarm
log indicates which power module generated the alarm:
1 = Left most inverter module.
2 = Middle inverter module in enclosure sizes F12
or F13.
MG16I302
Operating Instructions
WARNING 250, New spare part
A component in the frequency converter has been
replaced.
Troubleshooting
WARNING 251, New typecode
The power card or other components have been replaced
and the type code has been changed.
Troubleshooting
Danfoss A/S © 04/2015 All rights reserved.
2 = Right inverter module in enclosure sizes F10
or F11.
2 = Second frequency converter from the left
inverter module in enclosure size F14 or F15.
3 = Right inverter module in enclosure sizes F12
or F13.
3 = Third from the left inverter module in
enclosure sizes F14 or F15.
4 = Far right inverter module in enclosure sizes
F14 or F15.
5 = Rectifier module.
6 = Right rectifier module in enclosure size F14 or
F15.
Reset the frequency converter for normal
operation.
Reset to remove the warning and resume normal
operation.