Commissioning
Inspect for
Grounding
Input and output power
wiring
Panel interior
Switches
Vibration
5
5
Table 5.1 Start-up Checklist
54
®
VLT
HVAC Drive FC 102 Low Harmonic Drive
Description
The unit requires a ground wire from its enclosure to the building ground.
Check for good ground connections that are tight and free of oxidation.
Grounding to conduit or mounting the back panel to a metal surface is not sufficient.
Check for loose connections.
Check that motor and mains are in separate conduit or separated screened cables.
Inspect that the unit interior is free of debris and corrosion.
Ensure that all switch and disconnect settings are in the proper positions.
Check that the unit is mounted solidly or that shock mounts are used, as necessary.
Check for an unusual amount of vibration.