Danfoss VLT FC 102 Operating Instructions Manual page 66

Hvac drive low harmonic drive
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Application Examples
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
6
6
A IN
54
COM
55
A OUT
42
COM
39
Table 6.4 Speed Up/Down
Speed
Reference
Start ( 18)
Freeze ref ( 27)
Speed up ( 29 )
Speed down ( 32 )
Illustration 6.1 Speed Up/Down
64
®
VLT
HVAC Drive FC 102 Low Harmonic Drive
Parameters
Function
Setting
Parameter 5-10 T
[8] Start*
erminal 18
Digital Input
Parameter 5-12 T
[19] Freeze
erminal 27
Reference
Digital Input
Parameter 5-13 T
[21] Speed
erminal 29
Up
Digital Input
Parameter 5-14 T
[22] Speed
erminal 32
Down
Digital Input
* = Default value
Notes/comments:
D IN 37 is an option.
Danfoss A/S © 04/2015 All rights reserved.
6.2.2 Start/Stop
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.5 Start/Stop Command with Safe Stop Option
Speed
Start (18)
Illustration 6.2 Start/Stop Command with Safe Stop
Parameters
Function
Setting
Parameter 5-10 T
[8] Start*
erminal 18
Digital Input
Parameter 5-12 T
[0] No
erminal 27
operation
Digital Input
Parameter 5-19 T
[1] Safe Stop
erminal 37 Safe
Alarm
Stop
* = Default value
Notes/comments:
If parameter 5-12 Terminal 27
Digital Input is set to [0] No
operation, a jumper wire to
terminal 27 is not needed.
D IN 37 is an option.
MG16I302