3 Functions
3.14

Motor holding brake (MHB)

Parameter range:
Warnings
Faults
Function chart number:
For drives which must be secured when powered-down to prevent them
undesirably moving, the MICROMASTER brake sequence control (enabled via
P1215) can be used to control the motor holding brake.
Before opening the brake, the pulse inhibit must be removed and a current
impressed which keeps the drive in that particular position. In this case, the
impressed current is defined by the min. frequency P1080. A typical value in this
case is the rated motor slip r0330. In order to protect the motor holding brake from
continuous damage, the motor may only continue to move after the brake has been
released (brake release times lie between 35 ms and 500 ms). This delay must be
taken into account in parameter P1216 "Holding brake release delay" (refer to Fig.
3-68).
Fig. 3-68
196
P1215
P0346, P1216, P1217, P1080
r0052 bit 12
-
-
-
Motor holding brake after ON / OFF1