3 Functions
P0010 = 1
P0100 =...
P0100 = 1, 2
P0100 = 0
P0205 =... P0205 =...
P0300 =... P0300 =...
P0304 =... P0304 =... Rated motor voltage
P0305 =... P0305 =... Rated motor current
P0307 =... P0307 =... Rated motor power
P0308 =...
P0308 =...
P0309 =... P0309 =... Rated motor efficiency
84
Commissioning parameter *
0
Ready
1
Quick commissioning
30
Factory setting (refer to Section 3.5.9)
NOTE
P0010 should be set to 1 in order to parameterize the data of the motor rating
plate.
Europe/ North America
(enters the line supply frequency)
0
Europe [kW], frequency default 50 Hz
1
North America [hp], frequency default 60 Hz
2
North America [kW], frequency default 60 Hz
NOTE
For P0100 = 0 or 1, the setting of switch
P0100 (refer to Section 3.5.1).
OFF = kW, 50 Hz
ON = hp, 60 Hz
Inverter application (enters the required torque)
0
Constant torque (e.g. compressors, processing machines)
1
Variable torque (e.g. pumps, fans)
NOTE
This parameter is only effective for drive inverters ≥ 5.5 kW / 400 V
Select motor type
1
Asynchronous motor (induction motor)
2
Synchronous motor
NOTE
For P0300 = 2 (synchronous motor), only the V/f control types (P1300 < 20) are
permitted.
(Nominal motor voltage [V]
from rating plate)
The rated motor voltage on the rating
plate must be checked, regarding the
star/delta circuit configuration to
ensure that it matches with the circuit
connection configured at the motor
terminal board
(Nominal motor current [A]
from rating plate)
(Nominal motor power [kW/hp]
from rating plate)
If P0100 = 0 or 2, value will be in kW.
If P0100 = 1, value will be in in hp.
Rated motor cosPhi
(Nominal motor power factor (cos ϕ ) from rating plate)
If the setting is 0, the value is automatically calculated
P0100 = 1,2: P0308 no significance, no entry required.
(Nominal motor efficiency in [%] from rating plate)
Setting 0 causes internal calculation of value.
P0100 = 0: P0309 no significance, no entry required.
DIP50/60
determines the value of
FU-spec.
P0304
P0310
FU-spec.
FU-spec.
P0305
P0307
P0308 P0311
Example of a typical motor rating plate (data for
a delta circuit configuration).
The precise definition and explanation of this
data is specified in DIN EN 60 034-1.
MICROMASTER 440
Issue 10/06
0
0
0
1
FU-spec.
FU-spec.
Operating Instructions
6SE6400-5AW00-0BP0