3 Functions
3 independent settings are possible for each data set. These settings can be made
using the index of the particular parameter:
CDS1 ... CDS3
DDS1 ... DDS3
Those parameters (connector and binector inputs) which are used to control the
drive and enter a setpoint, are assigned to the command data set (CDS). The
signal sources for the control commands and setpoints are interconnected using
BICO technology (refer to Section 3.1.2.3). In this case, the connector and binector
inputs are assigned as signal sources corresponding to the connector and binector
outputs. A command data set includes:
Command sources and binector inputs for control commands (digital
signals) e.g.:
♦ Selects the command source
♦ ON/OFF1
♦ OFF2
♦ Enable JOG right
♦ Enable JOG left
Setpoint sources and connector inputs for setpoints (analog signals) e.g.:
♦ Selection of frequency setpoint
♦ Selection of main setpoint
♦ Selection of additional setpoint
The parameters, combined in a command data set, are designated with [x] in the
parameter list in the index field.
Index:
Pxxxx[0] : 1
Pxxxx[1] : 2
Pxxxx[2] : 3
NOTE
A complete list of all of the CDS parameters can be taken from the parameter list.
It is possible to parameterize up to three command data sets. This makes it easier
to toggle between various pre-configured signal sources by selecting the
appropriate command data set. A frequent application involves, for example, the
ability to toggle between automatic and manual operation.
MICROMASTER has an integrated copy function which is used to transfer
command data sets. This can be used to copy CDS parameters corresponding to
the particular application. The copy operation is controlled with P0809 as follows
(refer to Fig. 3-9):
1. P0809[0] = Number of the command data set which is to be copied (source)
2. P0809[1] = Number of the command data set into which data is to be copied
(target)
3. P0809[2] = 1 →
64
st
command data set (CDS)
nd
command data set (CDS)
rd
command data set (CDS)
Copying is started
Copying has been completed, if P0809[2] = 0.
P0700
P0840
P0844
P1055
P1056
P1000
P1070
P1075
MICROMASTER 440
Issue 10/06