3 Functions
3.5.7.18

Converter-specific Functions

Flying start
Flying start
p1200 = ...
Starts inverter onto a spinning motor by rapidly changing the output frequency of the
inverter until the actual motor speed has been found.
0
Flying start disabled
1
Flying start is always active, start in direction of setpoint
2
Flying start is active if power on, fault, OFF2, start in direction of setpoint
3
Flying start is active if fault, OFF2, start in direction of setpoint
4
Flying start is always active, only in direction of setpoint
5
Flying start is active if power on, fault, OFF2, only in direction of setpoint
6
Flying start is active if fault, OFF2, only in direction of setpoint
Motor-current: Flying start (entered in %)
p1202 = ...
Defines search current used for flying start.
Search rate: Flying start (entered in %)
p1203 = ?
Sets factor by which the output frequency changes during flying start to synchronize with
turning motor.
Automatic restart
Automatic restart
p1210 = ...
Configures automatic restart function.
0
Disabled
1
Trip reset after power on
2
Restart after mains blackout
3
Restart after mains brownout or fault
4
Restart after mains brownout
5
Restart after mains blackout and fault
6
Restart after mains brown/blackout or fault
118
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
Issue 10/06
0
100 %
100 %
1