Issue 10/06
Only Frame Sizes A to F
Class 3: With filter, for residential, commercial and trade applications
This level of EMC performance will allow the manufacturer/installer to certify
compliance of their equipment themselves with the EMC directive for the
residential, commercial and light industrial environment, as far as the EMC
performance characteristics of the power drive system are concerned.
Performance limits are as specified in the Generic Emission and Immunity
Standards EN 61000-6-3 and EN 61000-6-1 in residential applications.
Table 7-4
With filter, for residential, commercial and trade applications
EMC Phenomenon
Emissions:
Immunity:
* These limits are dependent on the inverter being correctly installed inside a
metallic switchgear enclosure. The limits will not be met if the inverter is not
enclosed.
NOTES
To achieve these performance levels. you must not exceed the default Pulse
frequency nor use cables longer than 25 m.
The MICROMASTER inverters are intended exclusively for professional
applications. Therefore. they do not fall within the scope of the harmonics
emissions specification EN 61000-3-2.
Maximum mains supply voltage when filters are fitted is 460 V.
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
Radiated emissions*
Conducted emissions
Supply voltage distortion
Voltage fluctuations, dips,
unbalance, frequency variations
Magnetic fields
Electrostatic discharge
Burst interference
Radio-frequency electro-
magnetic field, amplitude-
modulated
Radio-frequency electro-
magnetic field, pulse-modulated
7 Electro-magnetic compatibility
Standard
Level
EN 55011
Level B
EN 61800-3
Category C1:
Limit complying with EN 55011,
Class B
Category C2:
Limit complying with EN 55011,
Class A
EN 61000-2-4
EN 61000-2-1
EN 61000-4-8
50 Hz, 30 A/m
EN 61000-4-2
8 kV air discharge
EN 61000-4-4
2 kV power cables,
2 kV control cables
EN 61000-4-3
80–1000 MHz, 10 V/m, 80 %
AM, power and signal lines
EN 61000-4-3
900 MHz, 10 V/m 50 % duty
cycle, repetition rate 200 Hz