Quick Commissioning - Siemens MICROMASTER 440 Operating Instructions Manual

0.12kw-250kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 10/06
3.5.3

Quick commissioning

If there is still no appropriate parameter set for the drive, then a quick
commissioning must be carried-out for the closed-loop Vector control and for the
V/f control including a motor data identification routine. The following operator units
can be used to carry-out quick commissioning:
BOP (option)
AOP (option)
PC Tools (with commissioning program STARTER, DriveMonitor)
When the quick commissioning is carried-out, the motor – drive inverter is basically
commissioned; the following data must be obtained before quick commissioning is
started:
Line supply frequency
Motor rating plate data
Command / setpoint sources
Min. / max. frequency or ramp-up / ramp-down time
Closed-loop control mode
Motor data identification
Parameterizing the drive with BOP or AOP
The frequency inverter is adapted to the motor using the quick commissioning
function and important technological parameters are set. The quick commissioning
shouldn't be carried-out if the rated motor data saved in the frequency inverter
(4-pole 1LA Siemens motor, star circuit configuration
specific) match the rating plate data.
Parameters, designated with a * offer more setting possibilities than are actually
listed here. Refer to the parameter list for additional setting possibilities.
NOTE
Parameter P0308 or P0309 can only be viewed on the BOP or AOP if P0003 ≥
2. Depending on the setting of parameter P0100, either P0308 or P0309 is
displayed.
The value entered into P0307 and all of the other power data – depending on
P0100 – are either interpreted as kW or hp value.
START
P0003 = 3
P0004 = 0
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
User access level *
1
Standard: Allows access into most frequently used parameters
2
Extended: Allows extended access e.g. to inverter I/O functions
3
Expert (For expert use only)
Parameter filter *
0
All parameters
2
Inverter
3
Motor
4
Speed sensor
3 Functions
frequency inverter (FU)-
Factory setting
1
0
83