Siemens MICROMASTER 440 Operating Instructions Manual page 263

0.12kw-250kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 10/06
Feature
Serial Interface
Electromagnetic Compatibility
Braking
Protection Level
Temperature range
Storage Temperature
Humidity
Operational Altitudes
Protection Features
Standards
CE Marked
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
Specification
RS485, optional RS232
Frame Sizes A to C:
optional class A or B filters available according to
EN55011
Frame Sizes A to F:
inverter with integrated class A filter available
Frame Sizes FX and GX: With EMI filter (available as an option) the limiting
values of the EN 55011, Class A are fulfilled for
conducted emission.
(line commutating choke required)
DC braking, compound braking
Dynamic braking
Frame Sizes A to F
Frame Sizes FX and GX with external chopper
IP20
-10 °C to +50 °C (14 °F to 122 °F) (CT)
Frame Sizes A to F:
-10 °C to +40 °C (14 °F to 104 °F) (VT)
Frame Sizes FX and GX: 0 °C to +40 °C (32 °F to 104 °F),
up to 55 °C (131 °F) Power reduction see Figure 2.2
-40 °C to +70 °C (-40 °F to 158 °F)
< 95 % RH – non-condensing
Frame Sizes A to F:
Up to 1000 m above sea level without derating
Frame Sizes FX and GX: Up to 2000 m above sea level without derating
Undervoltage , Overvoltage, Overload, Ground Faults, Short circuit, Stall
Prevention, Motor Blocking Protection, Motor Overtemperature, Inverter
Overtemperature, Parameter Interlock
Frame Sizes A to F:
UL, cUL, CE, C-tick
Frame Sizes FX and GX: UL, cUL, CE
Conformity with EC Low Voltage Directive 73/23/EEC
and filtered versions also Electromagnetic Compatibility Directive 89/336/EEC
5 MICROMASTER 440 specifications
with integrated chopper
263

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents