Issue 10/06
Fig. 3-79
The continuous power and the load duty cycle are modified using parameter P1237
(setting values, refer to Fig. 3-80a). If the load duty cycle monitoring switches from
the peak power (100%) to the continuous power, then this is dissipated for an
unlimited length of time in the braking resistor (refer to Fig. 3-80b). Contrary to the
braking resistor, as listed in Catalog DA51.2, the chopper control can be
permanently operated with 100% power.
a
P
100
P
DB
t
t
ON
OFF
t
cycle
b
P
100
P
DB
t
100
t
P1237
Fig. 3-80
Chopper load duty cycle
For MICROMASTER 440, up to and including Size FS F, the braking module is
integrated in the drive inverter and the braking resistor can be connected via
external terminals B+, B-.
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
R
B+
Chopper
control
P1237 = 1
(5 %)
Increasing the level of braking energy which can be absorbed
t
OFF
t
cycle
R
R
B-
B+
Chopper
control
P1237 = 3
(20 %)
P1237
t
ON
5 %
12.0
10 %
12.6
20 %
14.2
t
50 %
22.8
100 %
Infinite
t
3 Functions
R
R
B-
t
t
P
OFF
cycle
DB
228.0
240.0
0.05
114.0
126.6
0.10
57.0
71.2
0.20
22.8
45.6
0.50
0
Infinite
1.00
209

Hide quick links:

Advertisement

Table of Contents
loading