5.2 PRODUCT SETUP
PATH: SETTINGS
PRODUCT SETUP
ADDRESSES
IEC NETWORK
CLIENT ADDRESSES
The UR can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to
which the UR can connect.
A maximum of two simultaneous connections are supported at any given time.
PATH: SETTINGS
PRODUCT SETUP
MODBUS USER MAP
5
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
address in the
ADDRESS
value of "0" in subsequent register
by "1". An address value of "0" in the initial register means "none" and values of "0" display for all registers. Different
values can be entered as required in any of the register positions.
ADDRESS
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
REAL TIME
CLOCK
5-50
COMMUNICATIONS
CLIENT ADDRESS 1:
0.0.0.0
CLIENT ADDRESS 2:
MESSAGE
0.0.0.0
CLIENT ADDRESS 3:
MESSAGE
0.0.0.0
CLIENT ADDRESS 4:
MESSAGE
0.0.0.0
CLIENT ADDRESS 5:
MESSAGE
0.0.0.0
MODBUS USER MAP
ADDRESS
VALUE:
ADDRESS
MESSAGE
VALUE:
ADDRESS
MESSAGE
VALUE:
ADDRESS 256:
MESSAGE
VALUE:
line (converted from hex to decimal format). The corresponding value displays in the
lines automatically returns values for the previous
ADDRESS
REAL TIME CLOCK
SYNCRONIZING SOURCE:
None
PRECISION TIME
MESSAGE
PROTOCOL (1588)
SNTP PROTOCOL
MESSAGE
LOCAL TIME
MESSAGE
L90 Line Current Differential System
IEC 60870-5-104 PROTOCOL
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: Standard IPV4 address format
Range: 0 to 65535 in steps of 1
1:
0
0
Range: 0 to 65535 in steps of 1
2:
0
0
Range: 0 to 65535 in steps of 1
3:
0
0
Range: 0 to 65535 in steps of 1
0
0
Range: None, PP/IRIG-B/PTP/SNTP, IRIG-B/PP/PTP/
SNTP, PP/PTP/IRIG-B/SNTP
See below
See below
See below
5 SETTINGS
IEC NETWORK CLIENT
5.2.6 MODBUS USER MAP
line. A
VALUE
lines incremented
ADDRESS
5.2.7 REAL TIME CLOCK
GE Multilin