GE UR Series L90 Instruction Manual page 667

Line current differential system
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 7 of 72)
ADDR
REGISTER NAME
1D06
Source 1 Negative Varhour
1D08
Reserved (8 items)
1D10
...Repeated for Source 2
1D20
...Repeated for Source 3
1D30
...Repeated for Source 4
1D40
...Repeated for Source 5
1D50
...Repeated for Source 6
Energy Commands (Read/Write Command)
1D60
Energy Clear Command
Source Frequency (Read Only) (6 modules)
1D80
Frequency for Source 1
1D82
Frequency for Source 2
1D84
Frequency for Source 3
1D86
Frequency for Source 4
1D88
Frequency for Source 5
1D8A
Frequency for Source 6
Source Demand (Read Only) (6 modules)
1E00
Source 1 Demand Ia
1E02
Source 1 Demand Ib
1E04
Source 1 Demand Ic
1E06
Source 1 Demand Watt
1E08
Source 1 Demand Var
1E0A
Source 1 Demand Va
1E0C
Reserved (4 items)
1E10
...Repeated for Source 2
1E20
...Repeated for Source 3
1E30
...Repeated for Source 4
1E40
...Repeated for Source 5
1E50
...Repeated for Source 6
Source Demand Peaks (Read Only Non-Volatile) (6 modules)
1E80
Source 1 Demand Ia Maximum
1E82
Source 1 Demand Ia Maximum Date
1E84
Source 1 Demand Ib Maximum
1E86
Source 1 Demand Ib Maximum Date
1E88
Source 1 Demand Ic Maximum
1E8A
Source 1 Demand Ic Maximum Date
1E8C
Source 1 Demand Watt Maximum
1E8E
Source 1 Demand Watt Maximum Date
1E90
Source 1 Demand Var
1E92
Source 1 Demand Var Maximum Date
1E94
Source 1 Demand Va Maximum
1E96
Source 1 Demand Va Maximum Date
1E98
Reserved (8 items)
1EA0
...Repeated for Source 2
1EC0
...Repeated for Source 3
1EE0
...Repeated for Source 4
1F00
...Repeated for Source 5
1F20
...Repeated for Source 6
Breaker Flashover (Read/Write Setting) (2 modules)
2196
Breaker flashover 1 function
2197
Breaker flashover 1 side 1 source
2198
Breaker flashover 1 side 2 source
2199
Breaker flashover 1 status closed A
219B
Breaker flashover 1 status closed B
GE Multilin
RANGE
0 to 1000000000000
---
0 to 1
2 to 90
2 to 90
2 to 90
2 to 90
2 to 90
2 to 90
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
---
0 to 999999.999
0 to 4294967295
0 to 999999.999
0 to 4294967295
0 to 999999.999
0 to 4294967295
0 to 999999.999
0 to 4294967295
0 to 999999.999
0 to 4294967295
0 to 999999.999
0 to 4294967295
---
0 to 1
0 to 5
0 to 6
0 to 4294967295
0 to 4294967295
L90 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
varh
0.001
F060
---
---
F001
---
1
F126
Hz
0.001
F003
Hz
0.001
F003
Hz
0.001
F003
Hz
0.001
F003
Hz
0.001
F003
Hz
0.001
F003
A
0.001
F060
A
0.001
F060
A
0.001
F060
W
0.001
F060
var
0.001
F060
VA
0.001
F060
---
---
F001
A
0.001
F060
---
1
F050
A
0.001
F060
---
1
F050
A
0.001
F060
---
1
F050
W
0.001
F060
---
1
F050
var
0.001
F060
---
1
F050
VA
0.001
F060
---
1
F050
---
---
F001
---
1
F102
---
1
F167
---
1
F211
---
1
F300
---
1
F300
DEFAULT
0
0
B
0 (No)
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0 (Disabled)
0 (SRC 1)
0 (None)
0
0
B-15

Advertisement

Table of Contents
loading

Table of Contents