5.4 SYSTEM SETUP
k) PMU RECORDING

PATH: SETTINGS
SYSTEM SETUP
 PMU 1
 RECORDING
PMU 1 FUNCTION: This setting enables or disables the recorder for PMU 1. The rate is fixed at the reporting rate set
within the aggregator (i.e., Aggregator 1).
PMU 1 NO OF TIMED RECORDS: This setting specifies the number of timed records that are available for a given log-
ical PMU 1(4). The length of each record is equal to the available memory divided by the content size and number of
records. As the number of records is increased the available storage for each record is reduced. The relay supports a
maximum of 128 records in either timed or forced mode.
PMU 1 TRIGGER MODE: This setting specifies what happens when the recorder uses its entire available memory
storage. Under the "Automatic Overwrite", the last record is erased to facilitate new recording, when triggered. Under
the "Protected" selection, the recorder stops creating new records when the entire memory is used up by the old un-
cleared records.
5
PMU 1 TIMED TRIGGER POSITION: This setting specifies the amount of pre-trigger data as a percent of the entire
record. This setting applies only to the timed mode of recording.
l) AGGREGATORS

PATH: SETTINGS
SYSTEM SETUP
 PMU AGGREGATOR 1
When the protocol selection is set via the software or keypad, all aggregators whose protocol is not set to None will
be set to the last protocol saved (i.e., C37.118 or IEC61850-90-5) to any aggregators, as both C37.118 and
IEC61850-90-5 simultaneous streaming of both R-SV values is not possible.
NOTE
5-122
PHASOR MEASUREMENT
PMU 1 FUNCTION
DISABLE
PMU 1 NO OF TIMED
MESSAGE
RECORDS: 10
PMU 1 TRIGGER MODE:
MESSAGE
AUTOMATIC OVERWRITE
PMU 1 TIMED TRIGGER
MESSAGE
POSITION: 10%
PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1
PROTOCOL: NONE
PMU AGGREGATOR 1:
MESSAGE
IDCODE: 1
PMU AGGREGATOR1:
MESSAGE
PORT: 1
PMU AGGREGATOR 1
MESSAGE
INCLUDE PMU1: No
PMU AGGREGATOR 1
MESSAGE
INCLUDE PMU2: No
PMU AGGREGATOR 1
MESSAGE
INCLUDE PMU3: No
PMU AGGREGATOR 1
MESSAGE
INCLUDE PMU4: No
 37.118 AGGR 1
MESSAGE
 CONFIGURATION
 90-5 AGGR 1
MESSAGE
 CONFIGURATION
L90 Line Current Differential System

PHASOR MEASUREMENT UNIT1
Range: Enable, Disable
Range: 2 to 128 in steps of 1
Range: Automatic Overwrite, Protected
Range: 1 to 50% in steps of 1

PMU AGGREGATOR 1
Range: NONE, 37.118, IEC 61850-90-5
Default: NONE
Range: 1 to 65534 in steps of 1
Default: 1
Range: 1, 2, 3
Default: 1
Range: No, Yes
Default: No
Range: No, Yes
Default: No
Range: No, Yes
Default: No
Range: No, Yes
Default: No
See below.
See below.
5 SETTINGS
RECORDING PMU1