6. Checking and maintenance
1
58
6.6.2.
1. Replace the lip seal and position it in the visit opening, making sure
that you place its lug outside the DHW tank.
6x
L000389-C
2. Replace the sheet gasket.
3. Fit the unit together.
Torque applied to the anode: 8 N·m.
2
The flange mounting bolts must not be excessively tight.
Flange
Lip gasket
Sheet gasket 15 N·m
L000594-A
4. After reassembly, check the watertightness of the lateral flange.
5. Switch on.
¼ See chapter: "Commissioning procedure", page 47.

Remounting the inspection hatches

CAUTION
Use a torque wrench.
Torque load
6 N·m +1/-0
Approximately 6 N·m is obtained by manipulating the box
spanner with the small lever and 15 N·m by manipulating
it with the large lever.
200SE-2S - 300SE-2S
26/04/2016 - 7607575-05