5. Commissioning
Parameter Description
Pump command mode
POMP
Minimum solar pump
PN
rate
Activation of the
OTHR
electrical back-up
Nighttime back-up set
THRn
point temperature
Back-up activation time
tn O
at night
Back-up deactivation
tn F
time at night
Daytime back-up option
O td
Daytime back-up set
THRd
point temperature
Daytime back-up
td O
activation time
Daytime thermostat
td F
deactivation time
Maximum flow rate (l/
DMAX
min)
Antifreeze type
GELT
Antifreeze concentration 20 / 70 %
GEL%
Manual mode
MAN
Software version
XXX
(1) The parameter is set to On if the S3 domestic hot water sensor is connected
50
Adjustment range Increment Factory
OnOF / PuLS /
PSOL
20 / 100%
1
On / OFF
40 / 95 °C
0.5
00:00 / 23:45
00:15
00:00 / 23:45
00:15
On / OFF
40 / 95 °C
0.5
00:00 / 23:45
00:15
00:00 / 23:45
00:15
0.5 / 100
10 - 1 - 0.1 3
0 / 1 / 2 / 3 / 4
1
1
Auto / 1 On / 1 OF
Remarks
setting
PSOL
OnOF: Heating pump ON or OFF
4
(0% or 100%)
PuLS: Pump modulation from 50%
4
to 100%
PSOL: PWM solar-controlled
4
heating pump
30
(1)
On: Electrical back-up present
OFF
4
OFF: No electrical back-up
4
If the S3 domestic hot water sensor is
connected, the OFF setting is not
available.
¼See chapter: "Description of the
55
installer parameters", page 51
23:00
07:00
ON
On: On
4
OFF: Off
4
¼See chapter: "Description of the
installer parameters", page 51
¼See chapter: "Description of the
55
installer parameters", page 51
16:00
Available if O td = On
18:00
Available if O td = On
¼See chapter: "Description of the
installer parameters", page 51
3
0: Water
4
1: Propylene glycol
4
2: Ethyl glycol
4
3: Tyfocor LS / G-LS
4
4: Greenway
4
45
If GELT = 1 or 2
AUTO
Auto: Automatic mode
4
1 On: Solar pump activated
4
1 OF: Solar pump deactivated
4
200SE-2S - 300SE-2S
26/04/2016 - 7607575-05